Schneider Electric LV848195

Schneider Electric LV848195 MasterPacT MTZ3 50 H1, 5000 A, 1

MPN LV848195
Active

Schneider Electric MasterPacT MTZ3, type MTZ3 50 H1, fixed-mount 4P circuit breaker, 5000 A at 40 °C, H1 100 kA 415 V AC performance class.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848195 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch230 mm
Connection surface topRear
Connection surface bottomRear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848195 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width997 mm
Height352 mm
Mechanical life cycles10000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

What the 5000 A and 100 kA ratings mean for your switchboard

The LV848195 is a MasterPacT MTZ3 50 H1 fixed-mount circuit breaker rated 5000 A at 40 °C with an H1 performance class delivering 100 kA Icu at 415 V AC. That 100 kA holds across the full operating voltage range up to 690 V AC, so the breaker clears a fault at the same interrupting capacity whether it sits on a 415 V or 690 V bus. The Icw rating of 100 kA for 3 s means it withstands a delayed trip coordination window without damage — essential for selective coordination (Category B per IEC 60947-2) where downstream breakers clear first and this unit holds in. The 420 W power dissipation at rated current matters for enclosure thermal design — a switchboard housing this unit needs ventilation or forced cooling to stay within the -25 to 70 °C operating range.

Standards compliance and isolation suitability

Physical integration — fixed-mount, rear-connected, 4P

Fixed-mount design with rear connection on both the line and load sides. The 997 mm width, 352 mm height, and 300 mm depth define the panel cutout and busbar layout. Connection pitch is 230 mm, which matches standard MasterPacT busbar systems. Mounting support is rails or base plate — the breaker bolts into a dedicated cradle, not a DIN rail. The neutral pole is on the right (4P, neutral right), so busbar phasing must follow that orientation.

Durability and operating conditions

Mechanical durability is 10,000 cycles with periodic preventive maintenance. Electrical durability under AC-3 switching duty is 6000 cycles at 440/690 V AC. IP30 protection means it is not washdown-rated — install inside a switchboard enclosure.