Skip to main content
Schneider Electric LV848226

Schneider Electric LV848226 MasterPact MTZ2 Drawout Circuit

MPN LV848226
Active

Schneider Electric MasterPacT, MasterPact MTZ2, circuit breaker, drawout, 4P, 800 A, H1 66 kA at 415 V AC, push-button control.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848226 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV848226 is a MasterPact MTZ2 drawout circuit breaker, part of the MasterPacT range, rated 800 A at 40 °C with a 4-pole configuration. It carries a performance type H1, delivering 66 kA Ics (service breaking capacity) at 220/415 V AC, 440 V, 500/525 V, and 660/690 V AC — meaning it clears faults up to that level across the full low-voltage distribution range without upstream coordination issues. This is a Category B breaker, designed for selectivity in power distribution protection — it coordinates with downstream devices so only the faulted branch opens. The drawout mounting means the breaker chassis stays wired to the bus; the moving portion slides out for inspection or replacement without disturbing the main connections. The unit ships without a control unit, so the buyer supplies the trip unit separately — a standard practice for MTZ2 frames where the protection profile (LSIG, LS, etc.) is specified at order time. Control is push-button, with front and rear connection options on both upside and downside.

Impulse withstand Uimp is 12 kV, which covers the transient overvoltage category for distribution panels in pollution degree 3 environments (, per IEC 60947-1). The maximum breaking time is 25 ms, and maximum closing response time is 70 ms — fast enough to limit arc energy in a fault. Electrical durability is rated at 10,000 cycles at 440 V and 690 V AC under EN/IEC 60947-2, and 6,000 cycles for AC-3 motor-switching duty. Mechanical durability is 25,000 cycles with periodic preventive maintenance. Power dissipation at rated current is 100 W — account for this heat in the enclosure sizing; a sealed panel without forced ventilation will need derating above 40 °C. Altitude derating applies above 2000 m. Sensor rating options are 400 A, 630 A, and 800 A — the frame accepts multiple sensor sizes for the same chassis.

MPN
LV848226