Skip to main content
Schneider Electric LV848227 — Circuit Breaker Accessories

LV848227 MasterPact MTZ2 Drawout Circuit Breaker, 1000 A, 66

MPNLV848227
Active

Schneider Electric MasterPacT MasterPact MTZ2, LV848227, drawout circuit breaker, 4P, 1000 A at 40 °C, H1 66 kA 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV848227 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection
LV848227 — Electrical
ParameterValue
Rated current [In]1000 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P
LV848227 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability25000 cycles with periodic preventive maintenance
Electrical durability10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
LV848227 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 10 H1
Control typePush-button
Mounting modeDrawout
Mounting supportRails Base plate
WidthDrawout circuit breaker with chassis: 556 mm Drawout circuit breaker without chassis: 493 mm
HeightDrawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 300 mm
DepthDrawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm
LV848227 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C
LV848227 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The LV848227 is a MasterPact MTZ2 drawout circuit breaker rated 1000 A at 40 °C with an H1 performance class delivering 66 kA Ics across 220–690 V AC. Selectivity category B means the breaker has intentional short-time delay capability, so it coordinates selectively with downstream feeders — critical for a main or tie breaker in a switchboard where you want only the faulted branch to open. The drawout mounting allows the breaker to be racked out for maintenance or replacement without disturbing the primary connections — standard for large switchgear where downtime on the bus is not acceptable. The chassis adds 103 mm to the depth (403 mm with chassis vs 300 mm without) and 63 mm to the width (556 mm vs 493 mm), so verify the cubicle depth before specifying. Mounting support options include rails or a base plate.

Altitude rating is 0–2000 m without derating, 2000–5000 m with derating. IP30 protection means the breaker is protected against tools and wires greater than 2.5 mm — standard for enclosed switchgear; the enclosure itself provides the higher IP rating. Power dissipation is 150 W at rated current — account for this in the switchgear ventilation calculation. The control type is push-button and ships without a control unit — the Micrologic trip unit is ordered separately as a system component. Upside and downside connections are both available in front or rear configurations, with a connection pitch of 115 mm. Sensor rating options are 400 A, 630 A, 800 A, and 1000 A — the breaker frame accepts any of these, so the same LV848227 can be down-rated with a lower sensor if the load changes.

Frequently asked questions

What are the key ratings for LV848227?

The LV848227 is rated 1000 A at 40 °C with an H1 performance class delivering 66 kA Ics at 220–690 V AC. It is a 4-pole drawout breaker with a rated insulation voltage of 1000 V AC and operational voltage of 690 V AC. The impulse withstand is 12 kV.

What is the breaking capacity of LV848227 at 415 V?

The service breaking capacity Ics is 66 kA at 220/415 V AC 50/60 Hz. The making capacity Icm at that voltage is 145 kA. The short-time withstand Icw is 66 kA for 0.5 s or 1 s.

What is the depth of LV848227 with and without chassis?

With the drawout chassis, the depth is 403 mm; without the chassis, the breaker body is 300 mm deep. Width is 556 mm with chassis, 493 mm without. Height is 439 mm with chassis, 300 mm without.

What standards does LV848227 comply with?

The LV848227 complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2 and rated for pollution degree 3.

MPN
LV848227