Skip to main content
Schneider Electric LV848429

Schneider LV848429 MasterPact MTZ2 1600 A Drawout Circuit Br

MPN LV848429
Active

Schneider Electric MasterPact MTZ2, LV848429, drawout circuit breaker, 4 poles, 1600 A rated current, H2 performance 100 kA at 415 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848429 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV848429 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 1600 A at 40 °C. The drawout chassis allows removal without disturbing line or load connections, which cuts downtime during maintenance or swap-out.

Breaking capacity and selectivity — what the ratings mean

That's Category B selectivity, so it coordinates with downstream breakers to isolate only the faulted branch.

Mechanical and electrical endurance

Mechanical durability is 25,000 cycles with periodic preventive maintenance. Electrical durability at 440 V AC is 10,000 cycles under EN/IEC 60947-2, and 6,000 cycles in AC-3 motor-switching duty. Maximum breaking time is 25 ms, closing response time 70 ms. These numbers matter for applications with frequent switching or where fault clearance speed is critical for arc-flash energy reduction.

Drawout mounting with 115 mm connection pitch. Chassis dimensions: 403 mm depth, 556 mm width, 439 mm height (with chassis); without chassis the breaker body is 300 mm deep, 493 mm wide, 300 mm tall. Mounts on rails or base plate. Front and rear connection options for both upside and downside. IP30 finger protection on the front face — standard for enclosed switchgear.

Designed for pollution degree 3 (industrial environment). Altitude derating above 2000 m. Rated insulation voltage 1000 V AC, impulse withstand 12 kV.

MPN
LV848429