Skip to main content
Schneider Electric LV848429 — Circuit Breaker Accessories

Schneider LV848429 MasterPact MTZ2 1600 A Drawout Circuit Br

MPNLV848429
Active

Schneider Electric MasterPact MTZ2, LV848429, drawout circuit breaker, 4 poles, 1600 A rated current, H2 performance 100 kA at 415 V AC, IEC 60947-2.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848429 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848429 — Electrical
ParameterValue
Rated current [In]1600 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848429 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 500/525 V AC 50/60 Hz 85 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability25000 cycles with periodic preventive maintenance
Electrical durability10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848429 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 16 H2
Control typePush-button
Mounting modeDrawout
Mounting supportRails Base plate
WidthDrawout circuit breaker with chassis: 556 mm Drawout circuit breaker without chassis: 493 mm
HeightDrawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 300 mm
DepthDrawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm

Environmental

LV848429 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848429 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider Electric LV848429 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 1600 A at 40 °C. The drawout chassis allows removal without disturbing line or load connections, which cuts downtime during maintenance or swap-out.

Breaking capacity and selectivity — what the ratings mean

That's Category B selectivity, so it coordinates with downstream breakers to isolate only the faulted branch.

Mechanical and electrical endurance

Mechanical durability is 25,000 cycles with periodic preventive maintenance. Electrical durability at 440 V AC is 10,000 cycles under EN/IEC 60947-2, and 6,000 cycles in AC-3 motor-switching duty. Maximum breaking time is 25 ms, closing response time 70 ms. These numbers matter for applications with frequent switching or where fault clearance speed is critical for arc-flash energy reduction.

Drawout mounting with 115 mm connection pitch. Chassis dimensions: 403 mm depth, 556 mm width, 439 mm height (with chassis); without chassis the breaker body is 300 mm deep, 493 mm wide, 300 mm tall. Mounts on rails or base plate. Front and rear connection options for both upside and downside. IP30 finger protection on the front face — standard for enclosed switchgear.

Designed for pollution degree 3 (industrial environment). Altitude derating above 2000 m. Rated insulation voltage 1000 V AC, impulse withstand 12 kV.

Frequently asked questions

Where can I buy LV848429 and what is the lead time?

The LV848429 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of LV848429 at 415 V?

The H2 performance class delivers 100 kA Icu and 100 kA Ics at 415 V AC, 50/60 Hz.

What standards does LV848429 comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12.

MPN