Schneider LV848480 MasterPact XF Closing Coil, 12 VDC, Obsol

MPNLV848480
Obsolete

Schneider Electric MasterPact XF, standard closing voltage release, LV848480, 12 VDC, 4.5 W holding, for MTZ2/3 drawout breakers.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV848480 — Identification
ParameterValue
Product / component typeVoltage release
Product rangeMasterPact
Device applicationControl
LV848480 — Mechanical
ParameterValue
Device short nameXF
Control typeStandard
LV848480 — Other specifications
ParameterValue
Voltage release typeClosing coil
Maximum response time80 ms on closing MasterPact MTZ2 90 ms on closing MasterPact MTZ3
Holding power consumption4.5 W
[Un] voltage power supply12 V DC 50/60 Hz
Threshold tripping voltage0.85...1.1 Un on closing
Circuit breaker mounting modeDrawout

Product details

The Schneider LV848480 is a standard closing voltage release (XF type) for MasterPact MTZ2 and MTZ3 drawout circuit breakers. It operates on a 12 VDC supply with a holding power consumption of 4.5 W, and its closing threshold is 0.85 to 1.1 times the rated supply voltage (Un). This is the coil that pulls the breaker closed on command — not a shunt trip or undervoltage release.

The 12 VDC supply is the coil voltage — verify your control power matches before wiring. The 4.5 W holding power is steady-state after the coil seals in; the inrush (pickup) draw is higher but not listed here. The 0.85...1.1 Un closing threshold means the coil will reliably close the breaker when the supply voltage is between 10.2 V and 13.2 V DC. Below 10.2 V it may not pull in. The 80 ms (MTZ2) to 90 ms (MTZ3) closing response time is the mechanical stroke, not the electrical contact make — that's fast enough for standard control sequencing but not for arc-flash mitigation schemes that need sub-cycle closing.

Deployment Context

This coil mounts inside the MasterPact MTZ2 or MTZ3 drawout cassette — it's not a standalone panel component. The drawout mounting mode means the breaker chassis stays wired to the bus while the moving portion (with the coil installed) can be racked out for maintenance. If you're retrofitting an existing MTZ2/3 cradle, verify the coil connector pinout matches your cradle's control wiring; the drawout interface is keyed but different vintages may have changed the terminal arrangement.

Frequently asked questions

What is LV848480 used for?

It is the standard closing coil (voltage release) for MasterPact MTZ2 and MTZ3 drawout circuit breakers. It receives a 12 VDC signal to mechanically close the breaker contacts.

Where can I buy LV848480?

We source this obsolete part through independent distribution channels. Submit an RFQ for current availability and pricing — it is quoted to order, not stocked on the shelf.

What is the supply voltage and power draw for LV848480?

The coil is rated for 12 VDC supply with a holding power consumption of 4.5 W. The closing threshold is 0.85 to 1.1 times the rated voltage (Un), so it needs at least 10.2 V to reliably pull in.