Skip to main content
Schneider Electric LV848510 — Circuit Breaker Accessories

LV848510 MasterPact Shunt Trip Release, 12 VDC, Obsolete

MPNLV848510
Obsolete

Schneider Electric MasterPact range, 2nd MX opening voltage release, standard control type, shunt trip release, 12 VDC, for drawout circuit breakers.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV848510 — Identification
ParameterValue
Product / component typeVoltage release
Product rangeMasterPact
Device applicationControl
LV848510 — Mechanical
ParameterValue
Device short namesecond MX
Control typeStandard
LV848510 — Other specifications
ParameterValue
Voltage release typeShunt trip release
Maximum response time60 ms on opening MasterPact MTZ2 60 ms on opening MasterPact MTZ3
Holding power consumption4.5 W
[Un] voltage power supply12 V DC
Threshold tripping voltage0.7...1.1 Un on opening
Circuit breaker mounting modeDrawout

Product details

The LV848510 is a 2nd MX opening voltage release from the Schneider Electric MasterPact range, designed as a shunt trip release for MasterPact MTZ2 and MTZ3 drawout circuit breakers. It operates on a 12 VDC supply and is classified under standard control type for control applications.

The voltage release requires a 12 V DC power supply (Un). The threshold tripping voltage is specified as 0.7...1.1 Un on opening — meaning the release will trip when the supply voltage drops to between 8.4 V and 13.2 V DC, which is the operating band for reliable shunt trip actuation. Maximum response time is 60 ms on opening for both MasterPact MTZ2 and MTZ3 frames, so the release clears the trip signal within that window. Holding power consumption is 4.5 W, which governs the continuous load on the control transformer or DC supply feeding the release coil.

Deployment Context

This shunt trip release mounts into the drawout cradle of MasterPact MTZ2 or MTZ3 air circuit breakers. The drawout configuration means the release is installed on the breaker chassis, not the fixed enclosure — relevant for panel builders coordinating the control wiring to the moving breaker carriage. It is a control-circuit component, not a main power path device; its function is remote or automatic tripping via a 12 VDC signal.

Frequently asked questions

Where can I buy LV848510 and how do I get a price?

The LV848510 is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quotation — submit an RFQ for a firm quote.

What is LV848510's listed range on this component line?

The LV848510 belongs to the MasterPact range from Schneider Electric.

What is LV848510's listed control type on this component line?

The LV848510 is classified under Standard control type.

MPN