Skip to main content
Schneider Electric LV848750 — Circuit Breaker Accessories

Schneider LV848750 MasterPact MTZ2 25 HA10 Switch Disconnect

MPNLV848750
Active

Schneider Electric MasterPact MTZ2 25 HA10, switch disconnector, 2500 A, 105 kA/1150 V AC 50/60 Hz (Icm), 3P, drawout.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV848750 — Identification
ParameterValue
Product / component typeSwitch disconnector
Product rangeMasterPact
Device applicationDistribution
LV848750 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated operational voltage [Ue]1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated insulation voltage [Ui]1250 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated impulse withstand voltage [Uimp]12 kV conforming to EN/IEC 60947-3
Network frequency50/60 Hz
Poles description3P
LV848750 — Protection & Performance
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-3
Utilisation categoryAC-23A AC-3
Mechanical durability20000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3
Electrical durabilityAC-23A: 500 cycles 1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Contact position indicatorYes
LV848750 — Mechanical
ParameterValue
Connection pitch115 mm
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width441 mm
Height439 mm
Depth403 mm
LV848750 — Environmental
ParameterValue
IP degree of protectionIP30
Pollution degree3 conforming to EN/IEC 60947-4-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C
LV848750 — Approvals
ParameterValue
StandardsEN/IEC 60947-3

Product details

The Schneider LV848750 is a MasterPact MTZ2 25 HA10 switch disconnector rated for 2500 A continuous at 1150 V AC, 50/60 Hz. It's a 3-pole drawout unit built to EN/IEC 60947-3, with a making capacity (Icm) of 105 kA peak at that voltage. That Icm figure tells you it can close onto a bolted fault without welding contacts — critical for motor-starting and distribution circuits where the inrush could otherwise take out a lesser switch.

Rated short-time withstand (Icw) is 50 kA for 1 s and also 50 kA for 3 s — that three-second window gives downstream breakers time to clear a fault without the switch disconnector taking damage. Insulation voltage (Ui) is 1250 V AC, so it's comfortable on 690 V systems with margin. The drawout chassis mount means you can rack the unit out for maintenance without disturbing the power wiring.

Utilisation category is AC-23A and AC-3, covering both occasional switching of mixed resistive/inductive loads and the more demanding motor-switching duty. Electrical durability is listed at 500 cycles at 1150 V under AC-23A conditions; mechanical durability is 20,000 cycles with periodic preventive maintenance. Suitability for isolation is confirmed to EN/IEC 60947-3, and the visible contact position indicator gives a positive open/closed status without needing to open the panel.

IP30 protection means it's fine inside a clean switchgear room but not for washdown areas.

Frequently asked questions

Where can I buy the LV848750 and how is it quoted?

The LV848750 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for the LV848750?

The LV848750 is rated 2500 A operational current at 1150 V AC, with a short-circuit making capacity of 105 kA peak and a short-time withstand of 50 kA for up to 3 seconds.

What standards does the LV848750 comply with?

The LV848750 complies with EN/IEC 60947-3 for switch-disconnectors and is suitable for isolation per that standard.

MPN
LV848750