Schneider Electric LV848750

Schneider LV848750 MasterPact MTZ2 25 HA10 Switch Disconnect

MPN LV848750
Active

Schneider Electric MasterPact MTZ2 25 HA10, switch disconnector, 2500 A, 105 kA/1150 V AC 50/60 Hz (Icm), 3P, drawout.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848750 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Insulation voltage ui1250 V AC 50/60 Hz conforming to EN/IEC 60947-3
Current2500 A AC 50/60 Hz 1150 V
Utilization categoryAC-23 A AC-3
IP ratingIP30
Terminal pitch115 mm
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848750 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-4-1
Depth403 mm
Width441 mm
Height439 mm
Electrical life cyclesAC-23 A: 500 cycles 1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles20000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3
ApplicationDistribution
Safety categoryHA10
Operating temperature-25...70 °C

Product details

The Schneider LV848750 is a MasterPact MTZ2 25 HA10 switch disconnector rated for 2500 A continuous at 1150 V AC, 50/60 Hz. It's a 3-pole drawout unit built to EN/IEC 60947-3, with a making capacity (Icm) of 105 kA peak at that voltage. That Icm figure tells you it can close onto a bolted fault without welding contacts — critical for motor-starting and distribution circuits where the inrush could otherwise take out a lesser switch.

Rated short-time withstand (Icw) is 50 kA for 1 s and also 50 kA for 3 s — that three-second window gives downstream breakers time to clear a fault without the switch disconnector taking damage. Insulation voltage (Ui) is 1250 V AC, so it's comfortable on 690 V systems with margin. The drawout chassis mount means you can rack the unit out for maintenance without disturbing the power wiring.

Utilisation category is AC-23A and AC-3, covering both occasional switching of mixed resistive/inductive loads and the more demanding motor-switching duty. Electrical durability is listed at 500 cycles at 1150 V under AC-23A conditions; mechanical durability is 20,000 cycles with periodic preventive maintenance. Suitability for isolation is confirmed to EN/IEC 60947-3, and the visible contact position indicator gives a positive open/closed status without needing to open the panel.

IP30 protection means it's fine inside a clean switchgear room but not for washdown areas.