Skip to main content
Schneider Electric LV864702 — Air Circuit Breakers

Schneider Electric LV864702

MPNLV864702
Active

Circuit breaker MasterPact MTZ2 40H, 4000A, 4P fixed, without MicroLogic

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

LV864702 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit
LV864702 — Electrical ratings
ParameterValue
Sensor rating4000 A
Rated operational voltage (Ue)240...600 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
LV864702 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA 240 V AC 50/60 Hz 100 kA 480 V AC 50/60 Hz 85 kA 600 V AC 50/60 Hz
Rated short-time withstand current (Icw)85 kA 1 s IEC 60947-2
Performance typeH
LV864702 — Performance
ParameterValue
Breaking time, max.30 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles with periodic preventive maintenance IEC 60947-2
LV864702 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width21.1 in (537 mm)
Height13.9 in (352 mm)
Depth11.8 in (300 mm)
Neutral pole positionLeft
Connection pitch4.5 in (115 mm)
Upside connectionFront Rear
Downside connectionFront Rear
LV864702 — Environmental
ParameterValue
Operating ambient temperature-13...158 °F (-25...70 °C)
Storage ambient temperature-40...185 °F (-40...85 °C)
IP degree of protectionIP30
Pollution degree3 IEC 60947-1
LV864702 — Approvals
ParameterValue
StandardsUL 489
MPN
LV864702