Skip to main content
Schneider Electric LV864711 — Air Circuit Breakers

Schneider Electric LV864711

MPNLV864711
Active

Circuit breaker MasterPact MTZ2 40H, 4000A, 4P drawout, without MicroLogic

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

LV864711 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit
LV864711 — Electrical ratings
ParameterValue
Sensor rating4000 A
Rated operational voltage (Ue)240...600 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
LV864711 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA 240 V AC 50/60 Hz 100 kA 480 V AC 50/60 Hz 85 kA 600 V AC 50/60 Hz
Rated short-time withstand current (Icw)85 kA 1 s IEC 60947-2
Performance typeH
LV864711 — Performance
ParameterValue
Breaking time, max.30 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles with periodic preventive maintenance IEC 60947-2
LV864711 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRails Base plate
WidthDrawout circuit breaker without chassis: 19.4 in (493 mm) Drawout circuit breaker with chassis: 21.9 in (556 mm)
HeightDrawout circuit breaker without chassis: 11.8 in (300 mm) Drawout circuit breaker with chassis: 17.3 in (439 mm)
DepthDrawout circuit breaker without chassis: 11.8 in (300 mm) Drawout circuit breaker with chassis: 15.9 in (403 mm)
Neutral pole positionLeft
Connection pitch4.5 in (115 mm)
Upside connectionFront Rear
Downside connectionFront Rear
LV864711 — Environmental
ParameterValue
Operating ambient temperature-13...158 °F (-25...70 °C)
Storage ambient temperature-40...185 °F (-40...85 °C)
IP degree of protectionIP30
Pollution degree3 IEC 60947-1
LV864711 — Approvals
ParameterValue
StandardsUL 489
MPN
LV864711