LX0FF012 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FF
LX0FF012 — Electrical
ParameterValue
Control circuit voltage [Uc]440 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)118.7 Ohm latching 68 °F (20 °C) 10802 Ohm unlatching 68 °F (20 °C)
LX0FF012 — Performance & Durability
ParameterValue
Operating time35...40 ms latching 50...100 ms unlatching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FF012 is a contactor coil from the TeSys F range, designed to operate a TeSys F contactor's magnetic circuit. It runs on a 440 V AC 50/60 Hz control circuit, with latching time of 35 to 40 ms and unlatching time of 50 to 100 ms.

The 440 V AC control voltage is the nominal coil rating — the circuit supplying the coil must deliver this voltage within the latching limits of 0.85 to 1.1 Uc (374 to 484 V AC) and unlatching limits of 0.85 to 1.1 Uc. Coil resistance measures 118.7 Ω for the latching winding and 10,802 Ω for the unlatching winding at 20 °C, which governs inrush and hold current draw from the control transformer. This suits intermittent-duty applications like conveyor start/stop or pump cycling, not continuous high-speed switching.

Where this class of part is used

Contactor coils like the LX0FF012 are the replaceable actuation element inside TeSys F contactors, which switch motor loads, resistive heaters, and other power circuits in industrial control panels. The coil itself mounts onto the contactor's magnet assembly and is swapped when the winding fails or the control voltage needs changing.

Frequently asked questions

What is the control voltage for this coil?

The LX0FF012 is rated for 440 V AC at 50/60 Hz. The latching voltage range is 0.85 to 1.1 Uc (374 to 484 V AC), and the unlatching range is the same.

What are the latching and unlatching times?

Latching time is 35 to 40 ms; unlatching time is 50 to 100 ms.

What is the mechanical durability of this coil?

Rated for 1 million mechanical cycles at a maximum operating rate of 120 cycles per hour at 40 °C.

What is the coil resistance?

Latching winding resistance is 118.7 Ω; unlatching winding resistance is 10,802 Ω, both measured at 20 °C.

MPN