It is a dual-voltage coil accepting both 230 V and 110 V AC/DC at 40-400 Hz, which means a single part covers two common control voltages — useful when a panel has mixed control transformers or when stocking a single spare for multiple voltage schemes. The latching (pick-up) operation completes in 35-40 ms, while unlatching (drop-out) takes 50-100 ms. The coil resistance at 20°C is 41.89 Ω for the latching winding and 496 Ω for the unlatching winding — these values matter when sizing the control transformer and verifying the power supply can deliver the inrush without dropping below the 0.85 Uc minimum hold-in limit.

Schneider LX0FG060 TeSys F Contactor Coil, 230/110 V AC/DC,
Schneider Electric TeSys F series, LX0FG060 contactor coil, 230/110 V AC/DC dual-voltage, 35-40 ms latching.
Specifications
| Parameter | Value |
|---|---|
| Product type | Contactor coil |
| Product range | TeSys |
| Device short name | LX0FG |
| Parameter | Value |
|---|---|
| Control circuit voltage [Uc] | 230 V AC/DC 40...400 Hz 110 V AC/DC 40...400 Hz |
| Control circuit type | AC/DC at 40...400 Hz |
| Control circuit voltage limits | Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc |
| Coil resistance (avg.) | 41.89 Ohm latching at 20 °C 496 Ohm unlatching at 20 °C |
| Parameter | Value |
|---|---|
| Operating time | 35...40 ms latching 50...100 ms unlatching |
| Max. operating rate | 120 cyc/h 40 °C |
| Mechanical durability | 1 Mcycles |
Product details
Frequently asked questions
What is the closest alternative to LX0FG060?
No official successor order code has been published for this coil. For a legacy TeSys F contactor, the only reliable path is to source the exact LX0FG060 from surplus stock. A parametric search for a TeSys F coil with the same 230/110 V AC/DC dual-voltage rating and 35-40 ms latching time may yield a functional equivalent, but pin-out and mounting dimensions must be verified against the existing contactor.
What is the operating time of LX0FG060?
Latching (pick-up) takes 35-40 ms; unlatching (drop-out) takes 50-100 ms. These are the mechanical operating times for the coil itself, not including the contactor's main contact travel.