Skip to main content
Schneider Electric LX0FH009 — Contactor & Starter Coils

TeSys LX0FH009 contactor coil, 240 V AC 50/60 Hz, obsolete

MPNLX0FH009
Obsolete

Schneider Electric TeSys F, contactor coil, LX0FH009, 240 V AC 50/60 Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX0FH009 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FH
LX0FH009 — Electrical
ParameterValue
Control circuit voltage [Uc]240 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)33.03 Ohm latching 68 °F (20 °C) 5002 Ohm unlatching 68 °F (20 °C)
LX0FH009 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 45...50 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FH009 is a contactor coil from the Schneider Electric TeSys F range, designed to replace the coil in a TeSys F contactor. It operates on a 240 V AC 50/60 Hz control circuit, with latching and unlatching control circuit voltage limits of 0.85...1.1 Uc.

The coil's latching resistance is 33.03 Ohm at 68 °F (20 °C), and unlatching resistance is 5002 Ohm at the same temperature. This difference is typical for a dual-winding or economizer circuit — the latching winding pulls the contactor in, then the hold winding (higher resistance, lower current draw) keeps it sealed. If you're swapping a failed coil, confirm the contactor's existing wiring matches this two-winding scheme. Operating time is 50...100 ms unlatching and 45...50 ms latching. That's fast enough for most motor starting and general switching, but if your application requires coordinated timing with other devices (e.g., reversing contactors with a mechanical interlock), verify the total break time against your safety circuit requirements. Rated for 1 Mcycles mechanical durability and a maximum operating rate of 120 cyc/h at 104 °F (40 °C). That's a standard duty cycle for a contactor this size — suitable for frequent starting of conveyors, pumps, or compressors, but not for high-speed indexing or servo applications that exceed 120 operations per hour.

Frequently asked questions

What is the closest alternative to LX0FH009?

No official successor order code is published. A functionally equivalent coil would need to match the 240 V AC 50/60 Hz control voltage, the TeSys F contactor frame, and the dual-winding (latching/unlatching) resistance values. Contact us with your application details for a cross-reference search.

What range does LX0FH009 belong to?

It belongs to the Schneider Electric TeSys range, specifically the TeSys F contactor series.

What is the category for LX0FH009?

The category is 22341-CONTACTOR,D,K,&F ACCESS, which covers contactors and accessories for the D, K, and F frame sizes.

MPN
LX0FH009