This is the replacement coil for TeSys F contactors, meaning it's what you swap in when the coil fails or you need to change the control voltage on an existing contactor in the panel. The coil draws its latching and unlatching currents through separate windings: average resistance is 146.3 Ω on the latching winding and 7947 Ω on the unlatching winding at 68 °F (20 °C). Operating time runs 50–100 ms unlatching and 40–75 ms latching — fast enough for most motor starting and switching duty, but not for high-speed cycling applications. That rate limit is the thermal constraint from the coil's own heat buildup — push it harder and the insulation life drops.
Schneider Electric LX0FJ013 TeSys F Contactor Coil, 480 V AC
Schneider Electric TeSys F, contactor coil, LX0FJ013, 480 V AC 50/60 Hz, 1 Mcycles mechanical durability.
Specifications
| Parameter | Value |
|---|---|
| Product type | Contactor coil |
| Product range | TeSys |
| Device short name | LX0FJ |
| Parameter | Value |
|---|---|
| Control circuit voltage [Uc] | 480 V AC 50/60 Hz |
| Control circuit type | AC 50/60 Hz |
| Control circuit voltage limits | Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc |
| Coil resistance (avg.) | 146.3 Ohm latching 68 °F (20 °C) 7947 Ohm unlatching 68 °F (20 °C) |
| Parameter | Value |
|---|---|
| Operating time | 50...100 ms unlatching 40...75 ms latching |
| Max. operating rate | 120 cyc/h 104 °F (40 °C) |
| Mechanical durability | 1 Mcycles |
Product details
Frequently asked questions
What is the closest pin-compatible alternative to LX0FJ013 in this component family?
No official successor order code is listed in the available records. A pin-compatible alternative from the TeSys F family would need to be verified against the contactor frame and mounting — contact us with the contactor model for a cross-reference.
What is LX0FJ013's listed range (TeSys) on this component line?
It belongs to the TeSys F range, Schneider Electric's line of contactors and accessories for motor control and switching applications.
What compliance documentation does this brand provide for LX0FJ013 (RoHS, REACH, UL, IEC)?
Compliance documentation is not listed in the available records. As an obsolete part sourced through independent channels, documentation availability depends on the specific date code and original packaging — request documentation requirements with your RFQ.