Schneider Electric LX0FK007 — Contactor & Starter Coils

Schneider Electric LX0FK007 TeSys F Contactor Coil, 127 V AC

MPNLX0FK007
Active

Schneider Electric TeSys F series, contactor coil LX0FK007, 127 V AC 50...400 Hz / 127 V DC, 50...100 ms unlatching 40...80 ms latching.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX0FK007 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FK

Electrical

LX0FK007 — Electrical
ParameterValue
Control circuit voltage [Uc]127 V AC 50...400 Hz 127 V DC
Control circuit typeAC 50...400 Hz DC standard
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)9.56 Ohm latching 68 °F (20 °C) 1159 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FK007 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FK007 is a replacement contactor coil for the TeSys F contactor range, rated for 127 V AC across 50...400 Hz or 127 V DC control circuits. Coil resistance measures 9.56 Ω in the latching winding and 1159 Ω in the unlatching winding at 20 °C — these numbers let you verify the coil is intact before installation with an ohmmeter, especially if the old coil failed shorted or open. Operating time is 50...100 ms for unlatching and 40...80 ms for latching, which is typical for this contactor frame size and means the coil can handle fast cycling within the 120 cycles/hour maximum at 104 °F (40 °C).

Control voltage and limits

The control circuit accepts 127 V AC or DC, with a tolerance band of 0.85...1.1 Uc for both latching and unlatching. That means the coil stays pulled in from about 108 V to 140 V — useful to know if your control transformer sags under load or if you're running a long cable run where voltage drop is a concern.

Mechanical durability and deployment context

Rated for 1 million mechanical cycles, the coil is designed for the TeSys F contactor frame — a common fit inside motor control centers and panel-mounted contactor assemblies where the coil snaps onto the contactor base. The 120 cycles/hour limit at 40 °C is the thermal ceiling; pushing past it shortens life on the varnish and the plunger mechanism.

Frequently asked questions

What is the control voltage for this coil?

It accepts 127 V AC across 50...400 Hz or 127 V DC, with a tolerance of 0.85...1.1 Uc for both latching and unlatching.

What are the coil resistance values?

Latching winding is 9.56 Ω and unlatching winding is 1159 Ω, both measured at 68 °F (20 °C).

What is the maximum operating rate?

120 cycles per hour at 104 °F (40 °C).

What series does this coil belong to?

It belongs to the Schneider Electric TeSys F range.

MPN
LX0FK007