Skip to main content
Schneider Electric LX0FK008 — Contactor & Starter Coils

TeSys LX0FK008 Contactor Coil, 220-230 V AC/DC, Obsolete

MPNLX0FK008
Obsolete

TeSys F, contactor coil, LX0FK008, 220...230 V AC/DC, obsolete.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX0FK008 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FK

Electrical

LX0FK008 — Electrical
ParameterValue
Control circuit voltage [Uc]220...230 V AC 50...400 Hz 220...230 V DC
Control circuit typeAC 50...400 Hz DC standard
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)28.81 Ohm latching 68 °F (20 °C) 3733 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FK008 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FK008 is a contactor coil from the TeSys F range, designed to replace or service the coil assembly in TeSys F contactors. It operates on a control circuit voltage of 220...230 V AC (50...400 Hz) or 220...230 V DC, with latching and unlatching voltage limits of 0.85...1.1 Uc. The coil's operating time is 50...100 ms for unlatching and 40...80 ms for latching. Average resistance at 68 °F (20 °C) is 28.81 Ohm for latching and 3733 Ohm for unlatching.

The 220...230 V AC/DC control voltage covers both common industrial control voltages in a single coil — useful for panels that run mixed AC and DC control circuits. The AC tolerance from 50 to 400 Hz means it works on standard 50/60 Hz supplies as well as higher-frequency applications like 400 Hz aircraft ground power. The 1 Mcycles mechanical durability is typical for contactor coils in this class; it will outlast most electromechanical contactor bodies in cyclic service. The maximum operating rate of 120 cycles per hour at 104 °F (40 °C) is a thermal limit — exceeding it risks overheating the coil. For high-duty-cycle applications like rapid reversing or jogging, derate or look at a coil rated for higher switching frequency. The operating time (50...100 ms unlatching, 40...80 ms latching) is fast enough for general motor starting but not for precision timing circuits.

Frequently asked questions

What is the closest alternative to LX0FK008?

No direct pin-compatible replacement is listed in the manufacturer's official records. For legacy TeSys F contactors, sourcing the LX0FK008 coil through surplus or new-old-stock channels against an RFQ is the most reliable path to maintaining existing equipment.

What range does LX0FK008 belong to?

It is part of the TeSys range, specifically the TeSys F series of contactors and accessories.

What is the control voltage for LX0FK008?

The control circuit voltage is 220...230 V AC (50...400 Hz) or 220...230 V DC.