Specifications

Identification

LX0FK010 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FK

Electrical

LX0FK010 — Electrical
ParameterValue
Control circuit voltage [Uc]380...400 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)89.56 Ohm latching 68 °F (20 °C) 10570 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FK010 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FK010 is a contactor coil from the TeSys F range, designed to operate the main contactor in motor-starting and power-switching applications. It's the replaceable coil assembly for TeSys F frame contactors, not the complete contactor itself. Rated for 380...400 V AC at 50/60 Hz, with control voltage limits of 0.85...1.1 Uc for both latching and unlatching. That means it holds in reliably down to about 323 V and up to 440 V, which covers typical industrial supply sags and swells on a 400 V nominal system. Coil resistance measures 89.56 Ohm for the latching winding and 10,570 Ohm for the unlatching winding at 68 °F (20 °C). The two-winding design is typical for DC-operated or mechanically-latched contactors — the latching winding pulls the armature in, then the hold-in winding takes over with lower current draw.

Performance and duty cycle

Operating time is 50...100 ms for unlatching and 40...80 ms for latching. That's fast enough for most motor-starting sequences but not for high-speed jogging applications — the maximum operating rate is 120 cycles per hour at 104 °F (40 °C). Mechanical durability is rated at 1 million cycles. That's the mechanical life of the coil assembly itself, not the contactor's electrical life under load — electrical life will be lower depending on the switched current and duty class.

Frequently asked questions

What is the closest alternative to LX0FK010?

No official successor order code is listed. For a replacement, the practical approach is to identify the complete TeSys F contactor assembly that uses this coil and source that assembly, or select a current-production TeSys contactor with the same coil voltage rating.