Skip to main content
Schneider Electric LX0FK224 — Contactor & Starter Coils

TeSys LX0FK224 Contactor Coil, 220 VAC Latching / 24 VAC Unl

MPNLX0FK224
Active

TeSys F, contactor coil, LX0FK224, 220 V latching / 24 V unlatching AC/DC, 50...100 ms unlatching operating time.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX0FK224 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FK

Electrical

LX0FK224 — Electrical
ParameterValue
Control circuit voltage [Uc]220 V AC 50...400 Hz latching 24 V AC 50...400 Hz unlatching 220 V DC latching 24 V DC unlatching
Control circuit typeAC 50...400 Hz DC standard
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)29 Ohm latching 68 °F (20 °C) 26 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FK224 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FK224 is a TeSys F contactor coil — the exchange part that drives the main contactor's armature. It's a dual-voltage coil: 220 V AC/DC for the latching (hold-in) circuit and 24 V AC/DC for the unlatching (drop-out) circuit. That split-voltage design means the coil pulls in on 220 V but releases on 24 V, giving you separate control over the close and open commands. Operating time runs 50...100 ms for unlatching and 40...80 ms for latching. At 68 °F (20 °C), the latching winding measures 29 Ω and the unlatching winding 26 Ω. The control circuit accepts AC 50...400 Hz or DC standard, so it works across common line frequencies and DC control buses.

Rated for 1 Mcycles mechanical durability — that's a million operations before the mechanical wear limit. Maximum operating rate is 120 cycles per hour at 104 °F (40 °C), which sets the pacing for repetitive pick-and-place or conveyor indexing applications. Stay under that rate to keep the coil temperature within limits.

Frequently asked questions

What is the voltage configuration of this coil?

220 V AC/DC for latching (hold-in) and 24 V AC/DC for unlatching (drop-out). The control circuit accepts AC 50...400 Hz or DC standard.

What are the operating times for this contactor coil?

Unlatching: 50...100 ms. Latching: 40...80 ms.

What is the mechanical durability rating?

1 Mcycles (one million operations) mechanical durability.