Skip to main content
Schneider Electric LX0FL011 — Contactor & Starter Coils

TeSys LX0FL011 Contactor Coil, 415 V AC, Obsolete

MPNLX0FL011
Obsolete

Schneider Electric TeSys F contactor coil, LX0FL011, 415 V AC 50/60 Hz, latching/unlatching coil for TeSys F contactors.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX0FL011 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FL

Electrical

LX0FL011 — Electrical
ParameterValue
Control circuit voltage [Uc]415 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)77.97 Ohm latching 68 °F (20 °C) 13003 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FL011 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FL011 is a replacement contactor coil from the Schneider Electric TeSys F range, designed to fit TeSys F contactors.

The coil is rated for a control circuit voltage of 415 V AC 50/60 Hz, with voltage limits of 0.85...1.1 Uc for both latching and unlatching — meaning the coil reliably picks up and drops out within a 353–456 V AC window. Operating time is 50...100 ms unlatching and 40...80 ms latching, which governs the contactor's response in motor start or safety circuits. Maximum operating rate is 120 cycles per hour at 104 °F (40 °C), so it is not intended for high-speed jogging or frequent cycling applications. Mechanical durability is rated at 1 million cycles, typical for a contactor coil in this class.

This coil is a service part for TeSys F contactors used in motor control centres, panel boards, and industrial automation systems where 415 V AC control circuits are standard — common in European and Asian 400 V distribution networks. It mounts directly onto the contactor's magnet system; no additional wiring changes are needed if replacing a failed coil in an existing TeSys F assembly.

Frequently asked questions

What is the closest pin-compatible alternative to LX0FL011?

No official successor order code is listed. A functional replacement would need a TeSys F coil rated for 415 V AC 50/60 Hz with the same latching/unlatching characteristics and mounting footprint. Contact our sourcing desk with your contactor model for a cross-reference.

What is the operating voltage range for this coil?

The control circuit voltage is 415 V AC 50/60 Hz, with limits of 0.85 to 1.1 times Uc for both latching and unlatching — so the coil is guaranteed to operate between approximately 353 V and 456 V AC.

What compliance documentation is available for LX0FL011?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this part. As a TeSys F component, it was originally designed to meet relevant IEC/EN standards for contactor accessories. Verify with your Schneider Electric documentation or request a certificate of conformance with your RFQ.

MPN
LX0FL011