Skip to main content
Schneider Electric LX0FL055 — Contactor & Starter Coils

Schneider LX0FL055 TeSys F Contactor Coil, 48 V DC Low Consu

MPNLX0FL055
Obsolete

Schneider Electric TeSys F series, LX0FL055 contactor coil, 48 V DC low consumption, 50-100 ms unlatching, 3.94 Ohm latching coil resistance.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX0FL055 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FL

Electrical

LX0FL055 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)3.94 Ohm latching 68 °F (20 °C) 59.17 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FL055 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

Part identification and key specs

The LX0FL055 is a 48 V DC low-consumption contactor coil from the Schneider Electric TeSys F range — the replacement coil for TeSys F contactors that use this control voltage. It operates with a latching time of 50 to 100 ms and an unlatching time of 40 to 80 ms, so the contactor responds within a predictable window for control logic timing. Coil resistance measures 3.94 Ω for the latching winding and 59.17 Ω for the unlatching winding at 68 °F (20 °C) — these values let you verify the coil is healthy with a simple ohmmeter before installation. Rated for a maximum operating rate of 120 cycles per hour at 104 °F (40 °C), which suits it for moderate-duty switching applications like conveyor or pump control.

The 48 V DC control circuit voltage (Uc) with a tolerance band of 0.85 to 1.1 Uc means the coil reliably latches between roughly 40.8 V and 52.8 V DC, and unlatches in the same range. If your control supply sags below 40.8 V, the contactor may drop out unexpectedly — factor that into your DC power supply sizing. Mechanical durability of 1 million cycles gives a baseline service life under ideal conditions. In practice, switching frequency, ambient temperature, and load type all derate that number — the 120 cycles/hour limit at 104 °F (40 °C) is the thermal constraint to watch.

Frequently asked questions

What replaces the LX0FL055?

Schneider has not published an official successor order code for this coil. For a like-for-like replacement, the procurement route is through independent surplus channels, not a direct cross-reference.

What is the control voltage and tolerance?

Rated 48 V DC with a latching and unlatching tolerance of 0.85 to 1.1 Uc — so the coil operates reliably between roughly 40.8 V and 52.8 V DC.

What is the operating time of this coil?

Latching takes 50 to 100 ms; unlatching takes 40 to 80 ms.

MPN
LX0FL055