Skip to main content
Schneider Electric LX1D2F6 — Contactor & Starter Coils

TeSys LX1D2F6 Contactor Coil, 110 V AC 60 Hz, Obsolete

MPNLX1D2F6
Obsolete

TeSys Deca, contactor coil, LX1D2F6, 110 V AC 60 Hz, for 9 to 18 A contactor, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1D2F6 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D2
Coil technologyWithout built-in suppressor module
LX1D2F6 — Electrical
ParameterValue
Control circuit voltage [Uc]110 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsOperational: 0.8...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Coil resistance (avg.)116.6 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)4.5 H
LX1D2F6 — Power & Thermal
ParameterValue
Inrush power (VA)70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))

Product details

The TeSys LX1D2F6 is a contactor coil from the TeSys Deca range, designed for 110 V AC 60 Hz control circuits. It mates with TeSys D and F contactors rated 9 to 18 A — the coil's inrush power is 70 VA at 60 Hz, and it holds in at 7.5 VA. Coil resistance measures 116.6 Ohm at 20 °C. The control circuit is AC 60 Hz only; the coil operates reliably between 0.8 and 1.1 times the rated voltage (88 to 121 V AC) at ambient temperatures up to 55 °C. No built-in suppressor — you'll need an external RC snubber or varistor if driving from a PLC or solid-state output.

What to watch when specifying

The coil is a direct replacement for the original LX1D2 on TeSys D and F contactors. No suppressor module inside means the coil's inductive kick is unclamped — factor in a flyback diode or RC network across the coil terminals if your control circuit uses DC switching or a solid-state output. Inductance of the closed circuit is 4.5 H, which gives a time constant of roughly 39 ms with the 116.6 Ohm resistance — expect a noticeable dropout delay if you're sequencing contactors in a safety circuit.

Frequently asked questions

What contactors does this coil fit?

It fits TeSys D and F contactors rated 9 to 18 A, as stated in the product description. The coil's 110 V AC 60 Hz control voltage matches those contactor frames.

What is the LX1D2F6's control voltage range?

Operational range is 0.8 to 1.1 times Uc at 60 Hz (88 to 121 V AC) at ambient temperatures up to 55 °C.

Does the LX1D2F6 include a built-in surge suppressor?

No. The coil technology is listed as 'without built-in suppressor module.' An external RC snubber or varistor is recommended for inductive kick suppression.

MPN
LX1D2F6