Schneider Electric LX1D2L6 — Contactor & Starter Coils

Schneider Electric LX1D2L6 TeSys Contactor Coil

MPNLX1D2L6
Obsolete

Schneider Electric TeSys LX1D2L6 contactor coil, 208 V AC 60 Hz, without built-in suppressor module, for 9 to 18 A contactors.

$80.35Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1D2L6 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D2
Coil technologyWithout built-in suppressor module
LX1D2L6 — Electrical
ParameterValue
Control circuit voltage [Uc]208 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsOperational: 0.8...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Coil resistance (avg.)417.8 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)16.6 H
LX1D2L6 — Power & Thermal
ParameterValue
Inrush power (VA)70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))

Product details

Lifecycle status and sourcing reality

The LX1D2L6: This coil is a replacement part for TeSys D contactors in the 9 to 18 A frame — a common line-down spare in older panels. Sourcing is confirmed per RFQ; availability and pricing are verified at quote time through our independent distribution network.

Coil ratings and fit for the contactor

This voltage tolerance ensures reliable pick-up even on a lightly loaded control transformer. Inrush power is 70 VA at 60 Hz (cos φ 0.75), dropping to 7.5 VA hold-in (cos φ 0.3). The 16.6 H inductance of the closed circuit means the holding current is low, so the coil runs cool in continuous duty — important for densely packed panels where heat buildup is a concern. Average DC resistance is 417.8 Ω at 68 °F (20 °C). This is a useful check when verifying coil integrity with an ohmmeter during commissioning or troubleshooting.

Coil technology and panel integration

This coil is supplied without a built-in suppressor module. If the contactor is switched by a PLC output or a solid-state relay, an external RC snubber or varistor should be added across the coil to suppress back-EMF and protect the switching device. Part of the TeSys D range, the LX1D2L6 is a direct-fit replacement for the standard coil on 9 to 18 A TeSys D contactors. No mounting modification is needed — it clips onto the contactor magnet assembly in the same footprint as the original.

Frequently asked questions

What is LX1D2L6's listed range (TeSys) on this component line?

The LX1D2L6 belongs to the TeSys D range of contactor coils, designed for 9 to 18 A TeSys D contactors.

What is LX1D2L6's listed coil technology (Without built-in suppressor module) on this component line?

The LX1D2L6 is supplied without a built-in suppressor module. An external suppression device (RC snubber or varistor) is recommended when the coil is driven by a solid-state output.

MPN
LX1D2L6