220 V AC 60 Hz coil for TeSys Deca contactors
The LX1D2M6 is a replacement coil from the TeSys Deca range, designed to fit contactors rated 9 to 18 A. At 20 °C the coil draws 70 VA inrush at 60 Hz with a 0.75 power factor, then drops to 7.5 VA hold-in at 0.3 power factor once the contactor seals. The average DC resistance is 490.2 Ω at 20 °C.
Schneider Electric lists the LX1D2M6 as obsolete. No official successor order code is recorded. The part is sourced through independent distribution channels; quantities and pricing are confirmed at RFQ against the BOM line.
Coil technology detail
This coil ships without a built-in suppressor module. If the contactor is driven by a PLC output or solid-state relay, an external RC snubber or varistor across the coil terminals is recommended to limit switching transients — a standard practice for AC coils in digitally controlled panels.