Skip to main content
Schneider Electric LX1D2V5 — Contactor & Starter Coils

Schneider Electric LX1D2V5 TeSys D Contactor Coil, 400 VAC 5

MPNLX1D2V5
Active

Schneider Electric TeSys D contactor coil, LX1D2V5, 400 V AC 50 Hz, for 9 to 18 A contactors.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1D2V5 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D2
Coil technologyWithout built-in suppressor module
LX1D2V5 — Electrical
ParameterValue
Control circuit voltage [Uc]400 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsOperational: 0.8...1.1 Uc at 50 Hz (at <131 °F (55 °C))
Coil resistance (avg.)2069 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)68 H
LX1D2V5 — Power & Thermal
ParameterValue
Inrush power (VA)60 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))

Product details

The LX1D2V5 is a replacement coil for the TeSys D contactor range, specifically the 400 V AC 50 Hz variant intended for 9 to 18 A frame contactors. It is an AC-operated coil with no built-in suppressor module, so an external RC snubber or varistor is your call depending on the PLC output driving it.

Coil draws 60 VA inrush at 50 Hz (cos φ 0.75) and holds at 7 VA (cos φ 0.3) — the inrush-to-hold ratio is about 8.5:1, which matters if your control transformer is sized tight or shares a circuit with other inductive loads. Operational voltage range is 0.8 to 1.1 times Uc at 50 Hz (320 to 440 V AC) up to 55 °C ambient; outside that band the coil may not pull in reliably or could overheat on sustained overvoltage. Average DC resistance is 2069 Ω at 20 °C — a quick bench check if you suspect a winding short.

Frequently asked questions

What is the closest alternative to LX1D2V5 in the TeSys family?

There is no direct pin-compatible successor published under the LX1D2 prefix. For a new design, the practical approach is to select the complete contactor assembly (e.g., LC1D09...LC1D18) with the desired coil voltage, rather than sourcing the coil separately.

What compliance documentation is available for LX1D2V5?

The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC) for this order code. Given its age and obsolete status, original documentation may be limited; we can check what the surplus lot carries on the nameplate.

MPN
LX1D2V5