Schneider LX1D6E5 TeSys contactor coil, 48 V AC 50 Hz

MPNLX1D6E5
Obsolete

Schneider Electric TeSys Deca LX1D6E5 contactor coil, 48 V AC 50 Hz, for 80 A and 95 A contactors, 6–10 W heat dissipation, 4 Mcycles mechanical durability.

$34.29Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1D6E5 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D6
Coil technologyWithout built-in suppressor module
LX1D6E5 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out: 0.3...0.6 Uc at 50/60 Hz (at Operational: 0.8...1.1 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Coil resistance (avg.)5.5 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.35 H
LX1D6E5 — Power & Thermal
ParameterValue
Inrush power (VA)200 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)20 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation6...10 W 50/60 Hz
LX1D6E5 — Performance & Durability
ParameterValue
Max. operating rate3600 cyc/h 140 °F (60 °C)
Mechanical durability4 Mcycles
LX1D6E5 — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

TeSys Deca coil for 80/95 A frames

The LX1D6E5 is a replacement coil from the TeSys Deca range, designed to fit Schneider 80 A and 95 A contactor frames. It runs on 48 V AC at 50 Hz — a common control voltage in European panel builds. Coil technology is basic: no built-in suppressor module. If your panel has a PLC or electronic controller driving this contactor, you will need an external RC snubber or varistor across the coil to suppress back-EMF at dropout.

Power draw and thermal budget

Inrush is 200 VA at 50 Hz (cos φ 0.75), dropping to 20 VA hold-in (cos φ 0.3). The closed-circuit inductance is 0.35 H, with an average resistance of 5.5 Ω at 20 °C. Heat dissipation runs 6–10 W at 50/60 Hz — enough to nudge the temperature inside a tightly packed panel, so check the ambient derating curve if the enclosure runs warm. That suits moderate-speed applications like conveyor or pump cycling — not high-speed pick-and-place.

Obsolete — sourcing through independent channels

Schneider lists the LX1D6E5 as obsolete. The part is available through independent surplus and broker channels — quantities are lot-specific and confirmed at RFQ. For a BOM freeze or MRO spare, the practical path is to source this coil against an RFQ. A genuine Schneider coil from TeSys Deca stock — same part, different passport — is the goal; confirm the coil voltage and frame fit before committing.

Frequently asked questions

What contactor does the LX1D6E5 coil fit?

The LX1D6E5 is a replacement coil for TeSys Deca contactors rated 80 A and 95 A. It is a 48 V AC 50 Hz coil with no built-in suppressor module.