Skip to main content
Schneider Electric LX1D6Z6 — Contactor & Starter Coils

Schneider TeSys LX1D6Z6 contactor coil, 20 VAC 60 Hz, active

MPNLX1D6Z6
Active

Schneider Electric TeSys D, LX1D6Z6, contactor coil, 20 V AC 60 Hz, for 80 & 95 A contactors, without built-in suppressor module.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1D6Z6 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D6
Coil technologyWithout built-in suppressor module
LX1D6Z6 — Electrical
ParameterValue
Control circuit voltage [Uc]20 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsDrop-out: 0.3...0.6 Uc at 50/60 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Coil resistance (avg.)0.79 Ohm 68 °F (20 °C)
LX1D6Z6 — Power & Thermal
ParameterValue
Inrush power (VA)220 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)22 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation6...10 W 50/60 Hz
LX1D6Z6 — Performance & Durability
ParameterValue
Max. operating rate3600 cyc/h 140 °F (60 °C)
Mechanical durability10 Mcycles
LX1D6Z6 — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

Coil for the 80/95 A frame

The LX1D6Z6 is a replacement coil in the TeSys D line, wound for 20 V AC at 60 Hz and sized for the 80 A and 95 A contactor frames. It pulls 220 VA inrush at 0.75 power factor, then settles to 22 VA hold-in at 0.3 PF — the drop is typical of an AC-magnet coil, so the control transformer supplying it needs to handle the inrush without dipping below 0.85 Uc or the armature chatters. The coil has no built-in suppressor; if the contactor drives inductive loads, you add an RC snubber or varistor across the coil terminals externally.

Voltage tolerance and thermal limits

Operating range is 0.85 to 1.1 Uc at 60 Hz below 55 °C ambient; drop-out occurs between 0.3 and 0.6 Uc. That 0.3 floor is generous — the coil stays pulled in through a brownout down to about 6 V, which matters on a line fed by a marginal generator. Heat dissipation runs 6 to 10 W at 50/60 Hz; in a densely packed panel, that adds up. Ambient operating range is -5 to 60 °C, so it handles a warm cabinet without derating.

Mechanical endurance and cycling

Rated for 10 million mechanical cycles at a maximum operating rate of 3600 cycles per hour at 60 °C.

Frequently asked questions

What is the category code for LX1D6Z6?

The category is 22341-CONTACTOR,D,K,&F ACCESS, which groups contactor accessories for the D, K, and F frame sizes.

MPN
LX1D6Z6