The LX1D6Z7 is a replacement coil for the TeSys Deca contactor range, sized for 40 to 95 A contactors and wound for 20 V AC 50/60 Hz control. This coil pulls 245 VA inrush at 60 Hz (cos φ 0.75) and holds at 26 VA (cos φ 0.3) — the inrush figure matters for sizing the control transformer feeding it, especially if several coils pull in simultaneously. It carries no built-in suppressor module, so you'll need an external RC snubber or varistor across the coil if the PLC output or relay driving it is solid-state or sensitive to back-EMF.

Schneider TeSys LX1D6Z7 Contactor Coil, 20 VAC, Obsolete
MPNLX1D6Z7
Obsolete
Schneider Electric TeSys Deca, contactor coil LX1D6Z7, 20 V AC 50/60 Hz, for 40 to 95 A contactor, obsolete.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product type | Contactor coil |
| Product range | TeSys |
| Device short name | LX1D6 |
| Coil technology | Without built-in suppressor module |
| Parameter | Value |
|---|---|
| Control circuit voltage [Uc] | 20 V AC 50/60 Hz |
| Control circuit type | AC 50/60 Hz |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at <131 °F (55 °C)) |
| Parameter | Value |
|---|---|
| Inrush power (VA) | 245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C)) |
| Hold-in power (VA) | 26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
Product details
Frequently asked questions
What contactor does this coil fit?
It is a replacement coil for TeSys Deca contactors rated 40 to 95 A.
Does this coil have a built-in suppressor?