Skip to main content
Schneider Electric LX1D8E6 — Contactor & Starter Coils

Schneider LX1D8E6 TeSys Contactor Coil, 48 V AC 60 Hz, Obsol

MPNLX1D8E6
Obsolete

Schneider Electric TeSys Deca contactor coil, LX1D8E6, 48 V AC 60 Hz, for 115 A contactor, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1D8E6 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D8
Coil technologyWithout built-in suppressor module
LX1D8E6 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 60 Hz (at Drop-out: 0.3...0.6 Uc at 60 Hz (at <131 °F (55 °C))
Coil resistance (avg.)3.91 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.28 H
LX1D8E6 — Power & Thermal
ParameterValue
Inrush power (VA)300 VA 60 Hz cos phi 0.8 (at 68 °F (20 °C))
Hold-in power (VA)22 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation3...8 W 60 Hz
LX1D8E6 — Performance & Durability
ParameterValue
Max. operating rate2400 cyc/h 140 °F (60 °C)
Mechanical durability8 Mcycles
LX1D8E6 — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

The LX1D8E6 is a TeSys Deca contactor coil from Schneider Electric, designed for 48 V AC 60 Hz control circuits and intended for use with a 115 A contactor. It is part of the TeSys range, a widely deployed family in industrial motor control panels.

Rated for 48 V AC at 60 Hz, this coil pulls 300 VA inrush at 60 Hz with a cos φ of 0.8, then holds at 22 VA with cos φ 0.3. The inrush figure tells you the instantaneous load on the control transformer when the contactor picks; the hold-in VA is what the coil continuously dissipates. Heat dissipation runs 3 to 8 W at 60 Hz, which matters for thermal management inside a sealed enclosure. Coil resistance averages 3.91 Ω at 68 °F (20 °C), and closed-circuit inductance is 0.28 H. The control circuit voltage limits are 0.85 to 1.1 Uc for pickup and 0.3 to 0.6 Uc for dropout at 60 Hz, so the coil will hold in down to about 40.8 V and drop out between 14.4 and 28.8 V. No built-in suppressor module is included — if your application needs flyback suppression, you add it externally. Ambient air temperature range for operation is 23 to 140 °F (-5 to 60 °C).

Frequently asked questions

What is the closest replacement for the LX1D8E6?

No official successor order code is provided in the lifecycle record. A parametric search for a TeSys Deca contactor coil rated 48 V AC 60 Hz without built-in suppressor is needed to identify a compatible replacement.

What TeSys range does the LX1D8E6 belong to?

It belongs to the TeSys range, specifically the TeSys Deca series, designed for use with 115 A contactors.

Does the LX1D8E6 include a built-in suppressor module?

No, it is listed as 'Without built-in suppressor module', so external suppression is required if needed for the application.

MPN
LX1D8E6