Skip to main content
Schneider Electric LX1D8R5 — Contactor & Starter Coils

Schneider Electric LX1D8R5 TeSys Contactor Coil, 440 V AC 50

MPNLX1D8R5
Active

Schneider Electric TeSys Deca contactor coil, LX1D8R5, 440 V AC 50 Hz, for 115 A contactor, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1D8R5 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D8
Coil technologyWithout built-in suppressor module
LX1D8R5 — Electrical
ParameterValue
Control circuit voltage [Uc]440 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out: 0.3...0.6 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 50 Hz (at <131 °F (55 °C))
Coil resistance (avg.)441.56 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)30.34 H
LX1D8R5 — Power & Thermal
ParameterValue
Inrush power (VA)300 VA 50 Hz cos phi 0.8 (at 68 °F (20 °C))
Hold-in power (VA)22 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation3...8 W 50 Hz
LX1D8R5 — Performance & Durability
ParameterValue
Max. operating rate2400 cyc/h 140 °F (60 °C)
Mechanical durability8 Mcycles
LX1D8R5 — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

The LX1D8R5 is a TeSys Deca contactor coil from Schneider Electric, designed to operate a 115 A contactor on a 440 V AC 50 Hz control circuit. It is a replacement coil for the LX1D8 series contactors, not a standalone contactor itself. This coil uses AC 50 Hz control technology without a built-in suppressor module, meaning an external RC snubber or varistor is required across the coil terminals if driving it from a PLC output or solid-state relay that needs protection from back-EMF. Rated for a 115 A contactor, this coil pulls 300 VA inrush at 50 Hz cos phi 0.8, dropping to 22 VA hold-in at cos phi 0.3. The 3 to 8 W heat dissipation at 50 Hz means the panel enclosure needs some airflow if multiple coils are ganged together.

The coil's average resistance is 441.56 Ohm at 68 °F (20 °C), and its closed-circuit inductance is 30.34 H. These values matter when sizing the external suppression network — a standard RC snubber (e.g., 100 Ω + 0.1 µF) across the coil terminals will limit voltage spikes without slowing dropout beyond the contactor's specification. Control circuit voltage limits are 0.85 to 1.1 Uc for pickup and 0.3 to 0.6 Uc for dropout at 50 Hz and below 131 °F (55 °C). On a 440 V line, that means pickup is guaranteed between 374 V and 484 V, and dropout occurs between 132 V and 264 V — wide enough to ride through moderate sags but not brownout conditions.

Frequently asked questions

What is the closest alternative to the LX1D8R5 in the TeSys family?

No official successor order code is listed in the lifecycle record. A parametric match would require a 440 V AC 50 Hz coil for a 115 A TeSys Deca contactor with the same mounting footprint, but without a published cross-reference from Schneider, any substitution must be verified against the contactor's coil terminal layout and mechanical interface.

What coil technology does the LX1D8R5 use?

It uses AC 50 Hz coil technology without a built-in suppressor module. An external suppression network (RC snubber or varistor) must be added by the installer if the driving circuit requires back-EMF protection.

What is the TeSys range for this component?

The LX1D8R5 belongs to the Schneider Electric TeSys range, specifically the TeSys Deca series of contactors and contactor coils.

MPN