Schneider Electric LX1FF030 — Contactor & Starter Coils

Schneider Electric LX1FF030 TeSys F Contactor Coil, 30-36 VA

MPNLX1FF030
Active

Schneider Electric TeSys F series, LX1FF030, replacement contactor coil, 30 V AC 50 Hz / 36 V AC 60 Hz control voltage, 50/60 Hz AC coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1FF030 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FF
Coil technologyWithout built-in suppressor module
LX1FF030 — Electrical
ParameterValue
Control circuit voltage [Uc]30 V AC 50 Hz 36 V AC 60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)0.41 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.06 H
LX1FF030 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 650 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation12...16 W 50 Hz
LX1FF030 — Performance & Durability
ParameterValue
Operating time23...35 ms closing 5...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FF030 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FF030 is a replacement contactor coil from the TeSys F range, designed to drop into the corresponding TeSys F contactor frame when the original coil fails or a voltage change is needed. It's an AC-operated coil, rated for 30 V AC at 50 Hz and 36 V AC at 60 Hz — so if you're swapping a coil on a line running 50 Hz, you're feeding it 30 V; on a 60 Hz line, it's 36 V. The coil pulls in at 85–110% of rated control voltage and drops out between 35–55% of Uc, which is a wide enough band to handle a saggy control transformer without nuisance dropouts.

Closing time runs 23 to 35 ms, opening between 5 and 15 ms — fast enough for most motor starting and general switching duty, but not a high-speed DC switching coil. The inrush power hits 550 VA at 50 Hz (650 VA at 60 Hz), and hold-in drops to 45 VA (55 VA at 60 Hz). That inrush matters for sizing your control transformer: a single coil this size won't stress a typical 100 VA transformer, but if you're ganging several contactors on one transformer, add up the inrush numbers. Heat dissipation runs 12 to 16 W at 50 Hz, so panel ventilation around a densely packed row of these coils is worth a thought.

Frequently asked questions

What control voltage does the LX1FF030 coil require?

The coil is rated for 30 V AC at 50 Hz and 36 V AC at 60 Hz. It operates within 85–110% of the rated control voltage and drops out between 35–55% of Uc.

Does the LX1FF030 coil include a built-in surge suppressor?

No, this coil is specified as 'without built-in suppressor module.' An external suppression device (RC snubber or varistor) should be added across the coil terminals if the driving circuit does not provide its own suppression.

What is the heat dissipation of this coil?

The LX1FF030 dissipates 12 to 16 W at 50 Hz during hold-in. Factor this into panel thermal calculations if multiple coils are mounted in a confined enclosure.

MPN
LX1FF030