Schneider Electric LX1FF056 — Contactor & Starter Coils

Schneider TeSys LX1FF056 Contactor Coil, 56 V AC 50 Hz

MPNLX1FF056
Obsolete

Schneider Electric TeSys F LX1FF056 contactor coil, 56 V AC 50 Hz, 550 VA inrush, 45 VA hold-in, without built-in suppressor module.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FF056 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FF
Coil technologyWithout built-in suppressor module
LX1FF056 — Electrical
ParameterValue
Control circuit voltage [Uc]56 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)1.58 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.22 H
LX1FF056 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation12...16 W 50 Hz
LX1FF056 — Performance & Durability
ParameterValue
Operating time23...35 ms closing 5...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FF056 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FF056 is a replacement coil for Schneider Electric TeSys F contactors, rated 56 V AC at 50 Hz. It pulls 550 VA inrush (cos φ 0.3) and settles to 45 VA holding — numbers you need to size the control transformer supplying it. No built-in suppressor module, so you add a separate RC snubber or varistor across the coil if the PLC output or relay driving it needs one.

Coil resistance is 1.58 Ω at 68 °F (20 °C), and closed-circuit inductance is 0.22 H — that combination determines the steady-state current draw and the thermal dissipation of 12…16 W at 50 Hz. The drop-out threshold is 0.35…0.55 Uc (about 20…31 V), and pickup is guaranteed at 0.85…1.1 Uc (48…62 V). If your control voltage sags below 48 V under load, the contactor may chatter or fail to close.

Frequently asked questions

What is the closest alternative to the LX1FF056?

The LX1FF series includes coils for other voltages and frequencies, but no direct pin-compatible replacement for the 56 V AC 50 Hz variant is listed as an official successor. Check the full LX1FF range for a voltage/frequency match to your control circuit.

What is the control voltage and frequency for this coil?

It is rated 56 V AC at 50 Hz only. The operating limits are 0.85…1.1 Uc (48…62 V) for pickup and 0.35…0.55 Uc (20…31 V) for drop-out.

Does this coil include a built-in suppressor?

No. The coil is supplied without a built-in suppressor module. An external RC snubber or varistor must be added if your control circuit requires surge suppression.