Schneider Electric LX1FF068 — Contactor & Starter Coils

Schneider Electric LX1FF068 TeSys F Contactor Coil, 68 V AC

MPNLX1FF068
Active

Schneider Electric TeSys F series, LX1FF068 contactor coil, 68 V AC 50 Hz control circuit, 550 VA inrush, 12-16 W holding dissipation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1FF068 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FF
Coil technologyWithout built-in suppressor module
LX1FF068 — Electrical
ParameterValue
Control circuit voltage [Uc]68 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)2.41 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.33 H
LX1FF068 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation12...16 W 50 Hz
LX1FF068 — Performance & Durability
ParameterValue
Operating time23...35 ms closing 5...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FF068 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FF068 is a replacement coil for Schneider Electric TeSys F contactors, wound for 68 V AC 50 Hz control circuits. It's the part you swap when a coil opens or shorts on a TeSys F frame — no suppressor module built in, so you add external flyback suppression if the circuit needs it. The 68 V AC coil pulls 550 VA inrush at 20°C (cos φ 0.3) and settles to 45 VA holding, dissipating 12-16 W. That inrush matters for transformer sizing on the control bus — a 100 VA control transformer won't hold two of these closing simultaneously.

Voltage tolerance and timing

Drop-out range is 0.35 to 0.55 Uc at 55°C — so the coil releases between roughly 24 and 37 V AC. Operational pickup is 0.85 to 1.1 Uc, meaning it needs at least 58 V AC to pull in reliably at temperature. Closing time runs 23-35 ms, opening 5-15 ms.

Frequently asked questions

What control voltage does this coil need?

The LX1FF068 is wound for 68 V AC at 50 Hz. It picks up at 0.85-1.1 Uc (58-75 V AC) and drops out at 0.35-0.55 Uc (24-37 V AC) at 55°C.

What is the inrush and holding power?

Inrush is 550 VA at 20°C (cos φ 0.3); holding power is 45 VA at 20°C (cos φ 0.3). Heat dissipation runs 12-16 W at 50 Hz.

Does this coil include a built-in suppressor?

No. The coil technology is listed as without built-in suppressor module. You'll need to add an external RC snubber or varistor across the coil terminals if the control circuit requires suppression.