Skip to main content
Schneider Electric LX1FF154 — Contactor & Starter Coils

Schneider Electric LX1FF154 TeSys F Contactor Coil, 154 V AC

MPNLX1FF154
Obsolete

Schneider Electric TeSys F contactor coil, LX1FF154, 154 V AC 50 Hz, 550 VA inrush, 45 VA hold-in, 12-16 W dissipation.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FF154 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FF
Coil technologyWithout built-in suppressor module
LX1FF154 — Electrical
ParameterValue
Control circuit voltage [Uc]154 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)13.51 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)1.69 H
LX1FF154 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation12...16 W 50 Hz
LX1FF154 — Performance & Durability
ParameterValue
Operating time23...35 ms closing 5...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FF154 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FF154 is a TeSys F contactor coil from Schneider Electric, wound for 154 V AC at 50 Hz. It pulls 550 VA inrush at cos φ 0.3 and settles to 45 VA holding — the 12 to 16 W heat dissipation figure tells you the thermal load the panel must shed. Closing time runs 23 to 35 ms, opening 5 to 15 ms. No built-in suppressor module, so you add your own RC snubber or varistor across the coil if the PLC output or relay driving it needs protection.

The 154 V AC coil is specific — not the common 110 V or 220 V tap. Drop-out happens between 0.35 and 0.55 Uc (about 54 to 85 V), pick-up between 0.85 and 1.1 Uc (131 to 169 V). If your control transformer delivers nominal 154 V, this coil holds in reliably; if your line sags below 131 V under load, it drops out.

Frequently asked questions

What is the closest pin-compatible alternative to LX1FF154?

No official successor order code is listed. A direct replacement would need to match the 154 V AC 50 Hz coil voltage and the TeSys F mechanical interface. Without a published cross-reference, the safest path is to source the original LX1FF154 from surplus inventory.

What is the LX1FF154's listed range?

It belongs to the TeSys range, specifically the TeSys F contactor family.

What is the LX1FF154's listed category?

The category is 22341-CONTACTOR,D,K,&F ACCESS, meaning it is an accessory coil for TeSys D, K, and F contactors.

What compliance documentation does Schneider provide for LX1FF154?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. As an obsolete part, original documentation may be available from Schneider's archive or through the surplus supplier providing the unit.

MPN