Skip to main content
Schneider Electric LX1FF800 — Contactor & Starter Coils

TeSys LX1FF800 Contactor Coil, 800 V AC 50 Hz, Obsolete

MPNLX1FF800
Active

Schneider Electric TeSys F contactor coil, LX1FF800, 800 V AC 50 Hz, 550 VA inrush, 45 VA hold, 12–16 W dissipation, 10 Mcycles mechanical durability.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FF800 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FF
Coil technologyWithout built-in suppressor module
LX1FF800 — Electrical
ParameterValue
Control circuit voltage [Uc]800 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)338.3 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)40.94 H
LX1FF800 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation12...16 W 50 Hz
LX1FF800 — Performance & Durability
ParameterValue
Operating time23...35 ms closing 5...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FF800 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FF800 is a replacement coil for TeSys F contactors, wound for 800 V AC 50 Hz control circuits. It draws 550 VA inrush at 20 °C (cos φ 0.3) and settles to 45 VA holding power, dissipating 12–16 W at 50 Hz. The 338.3 Ω average resistance at 68 °F (20 °C) and 40.94 H closed-circuit inductance define the coil's steady-state draw — useful when sizing the control transformer for a panel with multiple contactors.

Integration Notes

This coil mounts directly onto the TeSys F contactor magnet assembly. The 12–16 W heat dissipation at 50 Hz means the enclosure must allow airflow or derating if multiple coils are ganged in a sealed panel. Ambient operating range is 23–131 °F (-5–55 °C).

Frequently asked questions

What is the closest alternative to the LX1FF800 in the TeSys F family?

No official successor order code is published by Schneider Electric. A form-fit-function replacement would need to match the 800 V AC 50 Hz coil voltage, the TeSys F mechanical interface, and the 550 VA inrush / 45 VA hold characteristics. Without a published cross-reference, each alternative must be verified against the original contactor's coil cavity and control circuit.

How do I source the LX1FF800 given its obsolete status?

Sourcing runs through surplus and broker channels. Submit an RFQ for a quote on available new-old-stock or verified used units. No standard distributor stock is maintained.

MPN
LX1FF800