Schneider Electric LX1FG170 — Contactor & Starter Coils

Schneider LX1FG170 TeSys F Contactor Coil, 170 V AC 50 Hz

MPNLX1FG170
Obsolete

Schneider Electric TeSys F contactor coil, LX1FG170, 170 V AC 50 Hz, 805 VA inrush, 55 VA hold-in, without built-in suppressor module.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FG170 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FG
Coil technologyWithout built-in suppressor module
LX1FG170 — Electrical
ParameterValue
Control circuit voltage [Uc]170 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)9.11 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)1.53 H
LX1FG170 — Power & Thermal
ParameterValue
Inrush power (VA)805 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation18...24 W 50 Hz
LX1FG170 — Performance & Durability
ParameterValue
Operating time20...35 ms closing 7...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FG170 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FG170 is a replacement coil for the TeSys F contactor range, rated for 170 V AC at 50 Hz control circuits. It pulls 805 VA inrush and 55 VA hold-in at 50 Hz, cos φ 0.3, at 20 °C. That inrush figure matters for sizing the control transformer — you need enough VA headroom to pull the contactor in without dipping the control bus below the dropout threshold. Coil resistance is 9.11 Ω at 20 °C, and the closed-circuit inductance is 1.53 H. The dropout voltage range is 0.35 to 0.55 Uc (about 60 to 94 V), and pickup is guaranteed between 0.85 and 1.1 Uc (145 to 187 V) at 55 °C. If your control supply sags under load, that 0.85 Uc pickup floor is the number to check against your transformer regulation. There is no built-in suppressor module on this coil. That means you need to add an external RC snubber or varistor across the coil terminals if the contactor is driven by a PLC output or solid-state relay — otherwise the inductive kick can weld relay contacts or damage the driver. Standard practice is a 24-47 Ω / 0.1-0.47 µF RC network for 170 V AC coils.

Mechanical and thermal limits

Closing time is 20 to 35 ms, opening time 7 to 15 ms.

Frequently asked questions

What is the closest alternative to LX1FG170 in the TeSys F family?

There is no official pin-compatible replacement from Schneider for this exact 170 V AC 50 Hz coil. The LX1FG series includes other voltage taps (e.g., 110 V, 220 V, 380 V AC) that share the same physical footprint, but changing the control voltage requires rewiring the control circuit and verifying the transformer and protection devices. No direct drop-in substitute exists.

What is the TeSys range for this part?

The LX1FG170 belongs to the TeSys F contactor range, Schneider's modular contactor family for motor switching and power distribution up to about 630 A.

What compliance documentation is available for LX1FG170?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this part. As an obsolete product, original certification may be available from Schneider's archive, but it is not confirmed in the current record.

MPN
LX1FG170