Schneider Electric TeSys LX1FH0422 contactor coil, 42 V AC 50/60 Hz, 650 VA inrush, 10 VA holding, 8 W dissipation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1FH0422 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FH
Coil technologyWithout built-in suppressor module
LX1FH0422 — Electrical
ParameterValue
Control circuit voltage [Uc]42 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)0.8 Ohm inrush 68 °F (20 °C) 20 Ohm holding 68 °F (20 °C)
LX1FH0422 — Power & Thermal
ParameterValue
Inrush power (VA)650 VA 50/60 Hz cos phi 0.9 (at 68 °F (20 °C))
Hold-in power (VA)10 VA 50/60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation8 W 50/60 Hz
LX1FH0422 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...65 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FH0422 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The Schneider Electric LX1FH0422 is a replacement contactor coil from the TeSys range, designed to fit TeSys F contactors. It operates on a 42 V AC 50/60 Hz control circuit, drawing 650 VA inrush power at cos phi 0.9 and holding at 10 VA cos phi 0.3. Heat dissipation runs 8 W at 50/60 Hz. The coil has an average resistance of 0.8 Ohm inrush and 20 Ohm holding at 68 °F (20 °C). Opening time is 100...170 ms, closing time 40...65 ms. The coil has no built-in suppressor module, so you'll need to add external suppression (RC snubber or varistor) across the coil terminals if driving from a PLC output or electronic controller.

The 42 V AC control voltage is a common safety extra-low voltage (SELV) level in many industrial control schemes, often used in wet or hazardous environments where 120 V or 240 V control circuits pose a shock risk. The drop-out threshold of 0.35...0.55 Uc (14.7...23.1 V) and operational range of 0.85...1.1 Uc (35.7...46.2 V) at 131 °F (55 °C) mean the coil will reliably pick up at 42 V nominal and drop out cleanly if the control voltage sags below about 15 V. The ambient operating range is 23...131 °F (-5...55 °C). These ratings suit the coil for high-duty-cycle applications like conveyor systems or pump cycling, where the contactor may switch several times per minute.

Frequently asked questions

What is the control voltage for this coil?

The LX1FH0422 is a 42 V AC 50/60 Hz coil. It draws 650 VA inrush and 10 VA holding power.

Does this coil include a built-in suppressor?

No, the LX1FH0422 has no built-in suppressor module. External suppression (RC snubber or varistor) is required when driving from electronic controllers.

What is the mechanical life of this coil?

The LX1FH0422 is rated for 10 million mechanical cycles, with a maximum operating rate of 2400 cycles per hour at 131 °F (55 °C).