Schneider Electric LX1FH8502 — Contactor & Starter Coils

TeSys LX1FH8502 Contactor Coil, 850-910 V AC, Obsolete

MPNLX1FH8502
Active

Schneider Electric TeSys LX1FH8502 contactor coil, 850-910 V AC 40-400 Hz, 8 W, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FH8502 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FH
Coil technologyWithout built-in suppressor module
LX1FH8502 — Electrical
ParameterValue
Control circuit voltage [Uc]850...910 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))
LX1FH8502 — Power & Thermal
ParameterValue
Heat dissipation8 W 40...400 Hz
LX1FH8502 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...65 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
LX1FH8502 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FH8502 is a replacement contactor coil from the Schneider Electric TeSys range, designed to power the LX1F contactor series. It operates on a control voltage of 850-910 V AC at 40-400 Hz, drawing 8 W of heat dissipation at those frequencies.

The 850-910 V AC control voltage is a high-voltage coil — not a standard 24 V or 110 V control circuit. Verify that your panel's control transformer and wiring are rated for this range before specifying. The coil holds in from 0.85 to 1.1 times Uc (about 723-1001 V AC) and drops out between 0.35 and 0.55 times Uc (about 298-500 V AC). That dropout threshold matters for undervoltage release coordination: if your line dips below 300 V AC, the contactor will open.

Integration notes

The coil has no built-in suppressor module. If the contactor drives inductive loads (motors, solenoids), you need an external RC snubber or varistor across the coil terminals to limit voltage spikes on the control circuit. The 8 W dissipation at 40-400 Hz is continuous — ensure adequate airflow or spacing from heat-sensitive components inside the panel. The 2400 cycles/hour maximum at 55 °C derates at higher ambient temperatures; the operating range is -5 to 55 °C.

Frequently asked questions

What replaces the LX1FH8502?

There is no official successor order code from Schneider Electric for this coil. A parametric search for a TeSys LX1F coil with 850-910 V AC control voltage and 8 W dissipation would be needed to find a functional equivalent.

What is the control voltage range for this coil?

The rated control voltage is 850-910 V AC at 40-400 Hz. The coil operates reliably between 0.85 and 1.1 times Uc (723-1001 V AC) and drops out between 0.35 and 0.55 times Uc (298-500 V AC).

Does this coil include a built-in surge suppressor?

No. The LX1FH8502 is specified without a built-in suppressor module. An external RC snubber or varistor must be added for inductive load switching.

MPN
LX1FH8502