Skip to main content
Schneider Electric LX1FJ2206 — Contactor & Starter Coils

Schneider Electric LX1FJ2206 TeSys F Contactor Coil, 200-220

MPNLX1FJ2206
Obsolete

Schneider Electric TeSys F LX1FJ2206 contactor coil, 200-220 V AC 40-400 Hz, obsolete status.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FJ2206 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FJ
Coil technologyWithout built-in suppressor module
LX1FJ2206 — Electrical
ParameterValue
Control circuit voltage [Uc]200...220 V AC 40...400 Hz
Control circuit typeAC at 40...400 Hz
LX1FJ2206 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...75 ms closing
Max. operating rate1200 cyc/h 55 °C
Mechanical durability5 Mcycles

Product details

The LX1FJ2206 is the replacement coil for Schneider Electric's TeSys F contactor range, wound for a 200-220 V AC control circuit at 40-400 Hz. It is the part you pull when a TeSys F contactor drops out or the coil burns open — not a general-purpose relay coil, but a matched component for that specific frame.

Opening time is 100-170 ms, closing 40-75 ms. That 100 ms minimum opening window matters if your circuit relies on fast arc extinction — a faster-opening coil could cause nuisance arcing on inductive loads. The 5 Mcycle mechanical durability means this coil, on a contactor running at 1200 cycles per hour at 55 °C, is good for roughly 4000 hours of continuous duty before mechanical wear becomes a concern. The coil has no built-in suppressor module. If your control circuit uses a PLC or solid-state output to drive the contactor, you will need an external RC snubber or varistor across the coil terminals to protect the output from the inductive kick. This is standard practice for TeSys F coils, but easy to miss on a rush replacement.

Frequently asked questions

What is the operating time of the LX1FJ2206?

Opening time is 100-170 ms; closing time is 40-75 ms. These times are for the coil itself at rated voltage and temperature.

MPN