Skip to main content
Schneider Electric LX1FK075 — Contactor & Starter Coils

TeSys LX1FK075 Contactor Coil 75 V AC 50/60 Hz, Obsolete

MPNLX1FK075
Obsolete

Schneider Electric TeSys LX1FK075, contactor coil, 75 V AC 50/60 Hz, for LX1F contactor range.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FK075 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FK
Coil technologyWithout built-in suppressor module
LX1FK075 — Electrical
ParameterValue
Control circuit voltage [Uc]75 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsOperational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)66.4 Ohm holding 68 °F (20 °C) 3.7 Ohm inrush 68 °F (20 °C)
LX1FK075 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...75 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FK075 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FK075 is a replacement coil for the TeSys LX1F contactor range, wound for 75 V AC 50/60 Hz control circuits. It pulls the main contactor in — that's its whole job, and it does it without a built-in suppressor module, so you'll need to add one externally if the application demands it.

Coil resistance sits at 66.4 Ω holding and 3.7 Ω inrush at 20 °C — that inrush figure tells you the instantaneous current draw when the coil first pulls in, which matters for sizing your control transformer and fuse. The operating time window is 100 to 170 ms for opening and 40 to 75 ms for closing, so don't expect a fast-acting contactor; this is a standard industrial-duty coil, not a high-speed switching device. Rated for 10 Mcycles mechanical durability and a maximum operating rate of 2400 cycles per hour at 55 °C. That rate limit is the real-world constraint: if your application cycles the contactor faster than once every 1.5 seconds, this coil will overheat and fail prematurely. Control voltage limits are 0.85 to 1.1 Uc for operation and 0.3 to 0.5 Uc for drop-out at 55 °C. That 0.3 to 0.5 Uc drop-out window means the contactor will release when the control voltage dips below roughly 22.5 to 37.5 V AC — wide enough to tolerate brownouts but tight enough to avoid nuisance drop-outs on a sagging line.

Sourcing reality — this one is obsolete

If you need a pin-compatible alternative, you'll need to verify the mounting footprint and coil voltage against a current TeSys coil (like the LX1FK series at a different voltage) or a third-party equivalent — but that's a cross-reference exercise, not a guaranteed swap.

Frequently asked questions

What is the control voltage for the LX1FK075?

75 V AC at 50/60 Hz. The operating range is 0.85 to 1.1 times that voltage (roughly 63.75 to 82.5 V AC), and it drops out between 0.3 and 0.5 Uc (22.5 to 37.5 V AC).

Does the LX1FK075 include a built-in suppressor module?

No, it is specified as 'without built-in suppressor module'. You will need to add an external RC snubber or varistor across the coil if your control circuit requires suppression.

What is the maximum cycling rate for this coil?

2400 cycles per hour at 55 °C, which works out to one operation every 1.5 seconds. Exceeding that rate will cause thermal buildup and premature failure.

MPN
LX1FK075