Skip to main content
Schneider Electric LX1FK080 — Contactor & Starter Coils

TeSys LX1FK080 Contactor Coil, 80 V AC 50/60 Hz, Obsolete

MPNLX1FK080
Obsolete

Schneider Electric TeSys LX1FK080, contactor coil, 80 V AC 50/60 Hz, for LX1F contactors, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FK080 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FK
Coil technologyWithout built-in suppressor module
LX1FK080 — Electrical
ParameterValue
Control circuit voltage [Uc]80 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsOperational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)4.83 Ohm inrush 68 °F (20 °C) 84.7 Ohm holding 68 °F (20 °C)
LX1FK080 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...75 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FK080 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FK080 is a replacement coil for Schneider Electric TeSys LX1F series contactors, rated 80 V AC at 50/60 Hz. It is a bare coil — no built-in suppressor module — so you will need to add a separate RC snubber or varistor across the terminals if driving it from a PLC output or electronic controller. Opening time runs 100 to 170 ms; closing time is 40 to 75 ms. The coil draws 4.83 Ω inrush and 84.7 Ω holding at 20 °C, which matters for sizing the control transformer and verifying the drive circuit can deliver the peak inrush current without voltage sag.

The coil operates reliably between 0.85 and 1.1 times the rated control voltage (68 to 88 V AC) at 55 °C, and drops out between 0.3 and 0.5 Uc (24 to 40 V AC). That dropout range is wide enough that a marginal control supply or a long cable run with voltage drop should still release the contactor cleanly. For a coil that will see frequent cycling — say a pick-and-place or a rapid reversing application — that rate limit is the binding constraint, not the total cycle count. If the panel sits in an unconditioned space that sees higher ambient, the coil temperature rise from self-heating plus the environment may push the insulation beyond its rating — derate the operating rate or add forced ventilation.

Integration notes

This coil snaps onto the LX1F contactor magnet assembly. The control circuit is AC only — 50/60 Hz — so do not apply DC to it; the impedance and dropout characteristics are designed for sinusoidal AC, and DC operation will overheat the coil or fail to drop out.

Frequently asked questions

What contactor does this coil fit?

It fits the TeSys LX1F series contactors. The category code confirms it is an accessory for the D, K, and F frame contactors, but the LX1F coil family is specific to the F-frame.

Does the coil include a suppressor module?

No. It is supplied without a built-in suppressor module. You must add an external RC snubber or varistor if driving it from an electronic output.