Skip to main content
Schneider Electric LX1FK140

TeSys LX1FK140 Contactor Coil, 277 V AC, 40–400 Hz

MPN LX1FK140
Obsolete

Schneider Electric TeSys F contactor coil, LX1FK140, 277 V AC 40–400 Hz, 2200 VA inrush, 36 VA holding, no built-in suppressor module.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX1FK140 specifications
ParameterValue
Control circuit typeAC 40...400 Hz
Main product or component typeContactor coil
Coil voltage277 V AC 40...400 Hz
Temp operating max55 °C
Temp operating min-5 °C
Mechanical life cycles0.5 Mcycles
Operating time100...170 ms opening 40...75 ms closing
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FK140 is a replacement coil for the TeSys F contactor range, rated for 277 V AC control circuits at 40–400 Hz. It pulls 2200 VA inrush and settles to 36 VA holding at 20 °C. No built-in suppressor module — you'll need an external RC snubber or varistor across the coil if driving it from a PLC or solid-state output.

Coil Performance

Opening time runs 100–170 ms, closing 40–75 ms. Coil resistance measures 16.5 Ω inrush and 420 Ω holding at 20 °C; inductance of the closed circuit is 2.25 H. Control voltage limits are 0.85–1.1 Uc for operation and 0.3–0.5 Uc for dropout at 55 °C. Ambient temperature range for operation is –5 to 55 °C.

Heat Dissipation

The coil dissipates 18 W at 40–400 Hz. That heat goes into the contactor enclosure — if you're running multiple contactors in a sealed panel, account for the cumulative thermal load to stay within the ambient rating.

Integration Note

This is a TeSys F range coil — it mounts directly onto the F-frame contactor magnet assembly. No built-in suppressor means you wire the suppression externally. For AC control, a standard RC snubber across the coil terminals handles the back-EMF. If the contactor is cycled frequently, factor in the 18 W dissipation when sizing panel ventilation.

MPN