Skip to main content
Schneider Electric LX1FK175 — Contactor & Starter Coils

Schneider LX1FK175 TeSys contactor coil, 175 VAC 50/60 Hz

MPNLX1FK175
Obsolete

Schneider Electric TeSys LX1FK175 replacement contactor coil, 175 V AC 50/60 Hz, for LC1F series contactors.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FK175 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FK
Coil technologyWithout built-in suppressor module
LX1FK175 — Electrical
ParameterValue
Control circuit voltage [Uc]175 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsOperational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)23.5 Ohm inrush 68 °F (20 °C) 594 Ohm holding 68 °F (20 °C)
LX1FK175 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...75 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FK175 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

What this coil fits and what it needs

The LX1FK175 is a replacement coil for Schneider TeSys LC1F contactors. The coil draws 23.5 Ω inrush resistance at 20 °C and 594 Ω holding resistance at 20 °C — the shift between inrush and sealed current is built into the coil design, so the contactor's control transformer must be sized for the inrush draw. Opening time is 100...170 ms, closing time 40...75 ms. That closing speed is fast enough for standard motor starting but not for high-speed synchronous switching — if you need contact closure within one cycle of line frequency, this coil won't deliver it.

Coil voltage tolerance and dropout behaviour

The coil holds in across 0.85...1.1 Uc at 55 °C — that is 149...193 V AC. Dropout occurs between 0.3...0.5 Uc, or 53...88 V AC. For a panel running on a marginal 175 V supply, the 15 % undervoltage margin is adequate; below 149 V the contactor drops and must be re-energised. No built-in suppressor module is fitted, so an external RC snubber or varistor across the coil terminals is recommended if the contactor switches inductive loads or if the PLC output driving it is solid-state.

Mechanical limits and ambient conditions

Rated for 10 million mechanical cycles and a maximum operating rate of 2400 cycles per hour at 55 °C. That rate translates to one operation every 1.5 seconds — fine for conveyor jogging or pump sequencing, but not for high-speed pick-and-place or servo brake control. The coil is a single-unit package; order one per contactor.

Frequently asked questions

What contactor does this coil fit?

It is a replacement coil for Schneider TeSys LC1F series contactors. The LX1FK175 is the specific variant for 175 V AC 50/60 Hz control circuits.

What is the control voltage and type?

175 V AC at 50/60 Hz. Operational range is 0.85...1.1 Uc (149...193 V AC) at 55 °C. Dropout occurs at 0.3...0.5 Uc (53...88 V AC).

Does this coil include a built-in suppressor?

No. The coil technology is listed as 'Without built-in suppressor module'. An external RC snubber or varistor should be added if the contactor drives inductive loads or the control signal comes from a solid-state output.

MPN