Schneider LX1LB080 TeSys Coil, 80 V AC 50 Hz, 75 VA Inrush

MPNLX1LB080
Active

Schneider TeSys LX1 coil, 80 V AC 50 Hz, 75 VA inrush / 8 VA sealed, 57.38 Ohm ±10%.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1LB080 — Identification
ParameterValue
Product typeCoil
Product rangeTeSys
Device short nameLX1
LX1LB080 — Electrical
ParameterValue
Control circuit voltage [Uc]80 V AC 50 Hz
Coil resistance (avg.)57.38 Ohm at 68 °F (20 °C) +/- 10 %
Coil inductance0.95 mH
LX1LB080 — Power & Thermal
ParameterValue
Power consumption (VA)75 VA AC 0.55 50 Hz inrush 8 VA AC 0.28 50 Hz sealed

Product details

The LX1LB080 is a replacement coil from Schneider's TeSys range, designed for 80 V AC 50 Hz control circuits. It's the spare part you order when the original coil on a TeSys contactor or starter fails, or when you're building a panel with a non-standard control voltage.

Coil resistance is 57.38 Ohm at 20 °C ±10 % — that's the cold measurement. It determines the inrush current and the holding current the control transformer or PSU must deliver. The inrush power is 75 VA at 0.55 power factor (50 Hz); once sealed, it drops to 8 VA at 0.28 PF. That 9:1 ratio means the transformer must be sized for the inrush peak, not the sealed draw, or the voltage will sag and the contactor may chatter. Inductance is 0.95 mH — relevant if you're calculating the L/R time constant for suppression circuits or verifying compatibility with a PLC solid-state output driving the coil.

Lifecycle status is active per Schneider, so this is a current-production part — no last-time-buy pressure. It's specified into the BOM line as a service spare (category 18402).

Frequently asked questions

What control voltage does this coil need?

80 V AC at 50 Hz. Verify your panel supply matches before ordering — it's a less common voltage than 110 V or 230 V.

What is the inrush and sealed VA?

75 VA inrush at 0.55 PF, 8 VA sealed at 0.28 PF. Size the control transformer for the inrush value.

MPN