Skip to main content
Schneider Electric LX1LC0489 — Contactor & Starter Coils

Schneider LX1LC0489 TeSys coil, 48 V AC, obsolete

MPNLX1LC0489
Obsolete

Schneider Electric TeSys LX1 replacement coil, LX1LC0489, 48 V AC 50/60 Hz, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1LC0489 — Identification
ParameterValue
Product typeCoil
Product rangeTeSys
Device short nameLX1
LX1LC0489 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V AC 50/60 Hz
Coil resistance (avg.)13.349 Ohm +/- 10 %
Coil inductance0.107 mH closed circuit
LX1LC0489 — Power & Thermal
ParameterValue
Power consumption (VA)12...18 VA AC 0.3 60 Hz sealed 170...230 VA AC 0.55 60 Hz inrush

Product details

The LX1LC0489 is a replacement coil from the TeSys range, designed for LC1 contactors and similar TeSys magnetic starters. It operates on a 48 V AC control circuit at 50/60 Hz, making it a drop-in service part for panels wired to that voltage standard.

Electrical characteristics that matter for fit

The coil draws 12...18 VA sealed at 60 Hz, but the inrush demand hits 170...230 VA at 0.55 power factor. That inrush peak is what the control transformer and upstream fuse must handle — the sealed VA is what the coil dissipates once the contactor is held in. Average DC resistance measures 13.349 Ohm ±10%, and the closed-circuit inductance is 0.107 mH. These values are useful for verifying coil integrity with an ohmmeter during troubleshooting or for sizing snubber networks across the coil terminals.

Lifecycle reality — this part is obsolete

Schneider has marked the LX1LC0489 as obsolete.

Frequently asked questions

What replaces the LX1LC0489?

No official successor order code is published in the lifecycle record. A form-fit-function substitute would need to match the 48 V AC 50/60 Hz control voltage, the TeSys mounting footprint, and the inrush/sealed VA curve — but no direct cross-reference is available from the manufacturer.

What is the control voltage for this coil?

48 V AC at 50/60 Hz. This is the only voltage variant for this order code — verify your panel's control voltage matches before ordering.

MPN
LX1LC0489