Skip to main content
Schneider Electric LX1LC330 — Contactor & Starter Coils

TeSys LX1LC330 Coil, 330 V AC 50/60 Hz, Active

MPNLX1LC330
Active

Schneider Electric TeSys LX1LC330, replacement coil, 330 V AC 50/60 Hz control circuit, 12-18 VA sealed, 392.321 Ohm ±10%.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1LC330 — Identification
ParameterValue
Product typeCoil
Product rangeTeSys
Device short nameLX1
LX1LC330 — Electrical
ParameterValue
Control circuit voltage [Uc]330 V AC 50 Hz 380 V AC 60 Hz
Coil resistance (avg.)392.321 Ohm +/- 10 %
Coil inductance0.107 mH closed circuit
LX1LC330 — Power & Thermal
ParameterValue
Power consumption (VA)12...18 VA AC 0.3 60 Hz sealed 170...230 VA AC 0.55 60 Hz inrush

Product details

The LX1LC330 is a replacement coil from the TeSys range, designed for LC1 series contactors. It is the wound component that energizes the contactor's magnetic circuit, pulling the main poles closed when the control voltage is applied. Control circuit voltage is 330 V AC at 50 Hz and 380 V AC at 60 Hz — a dual-frequency rating that covers 50 Hz and 60 Hz mains without a separate tap. Power consumption sits at 12-18 VA sealed (holding) and 170-230 VA inrush at 60 Hz, 0.3 A sealed / 0.55 A inrush. The inrush figure governs the sizing of the control transformer or PLC output driving this coil; the sealed draw is what the thermal budget sees in continuous operation.

Key electrical parameters for fit verification

Average resistance is 392.321 Ohm ±10% at 20 °C. This is the value to compare against a failed coil when troubleshooting an intermittent dropout — a shorted or open winding will deviate well outside the ±10% band. Inductance is 0.107 mH with the magnetic circuit closed (contactor engaged). Open-circuit inductance will differ; this figure is the operating value once the armature seals.

Frequently asked questions

What is the LX1LC330's listed range?

The LX1LC330 belongs to the TeSys range from Schneider Electric.

What is the control voltage for this coil?

The control circuit voltage is 330 V AC at 50 Hz and 380 V AC at 60 Hz.

What is the sealed power consumption of the LX1LC330?

Sealed power consumption is 12-18 VA at 60 Hz, 0.3 A. Inrush is 170-230 VA at 60 Hz, 0.55 A.

MPN