Skip to main content
Schneider Electric LX1LD020 — Contactor & Starter Coils

Schneider Electric LX1LD020 TeSys coil, 24 V AC 60 Hz, obsol

MPNLX1LD020
Obsolete

Schneider Electric TeSys Integral replacement coil, LX1LD020, 24 V AC 60 Hz, 420-500 VA inrush, 0.213 Ohm resistance.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1LD020 — Identification
ParameterValue
Product typeCoil
Product rangeTeSys
Device short nameLX1
LX1LD020 — Electrical
ParameterValue
Control circuit voltage [Uc]24 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at Drop-out: 0.25...0.7 Uc (at <131 °F (55 °C))
Coil resistance (avg.)0.213 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.045 H
LX1LD020 — Power & Thermal
ParameterValue
Inrush power (VA)420...500 VA 60 Hz cos phi 0.55
Hold-in power (VA)24...36 VA 60 Hz cos phi 0.28

Product details

The LX1LD020 is a replacement coil for the TeSys Integral line of combination starters — the part that pulls the contactor in when 24 V AC at 60 Hz is applied to the control circuit. It draws 420 to 500 VA inrush at 60 Hz with a 0.55 power factor, then settles to 24 to 36 VA holding power once the magnetic circuit closes. The coil resistance measures 0.213 Ohm at 68 °F (20 °C). Dropout occurs between 0.25 and 0.7 times Uc at temperatures up to 131 °F (55 °C).

Because this is a replacement coil for a specific Integral starter frame, the physical fit (mounting holes, plunger stroke, terminal spacing) is fixed to that platform. No direct drop-in successor is listed in the official lifecycle record. A cross-reference search against the TeSys coil family is warranted if a new-production alternative is preferred.

The 24 V AC 60 Hz control voltage is specific — not 50 Hz, not DC. If your panel supply is 24 V DC or 50 Hz mains, this coil will not pull in reliably or will overheat. The 420-500 VA inrush figure governs the control transformer sizing: a 50 VA transformer will drop voltage on pickup and may fail to close the contactor. Size the transformer for at least 500 VA momentary or use a dedicated control power supply. The hold-in power of 24-36 VA is the steady-state load the coil presents once sealed. This determines the thermal load on the control circuit and the rating of any pilot devices switching the coil.

Frequently asked questions

What is the closest pin-compatible alternative to LX1LD020?

No official direct replacement is listed in the lifecycle record. A cross-reference search against the TeSys coil family is needed to find a new-production coil with the same mounting and electrical characteristics.

What is LX1LD020's listed range?

The LX1LD020 belongs to the TeSys range, Schneider Electric's line of motor control and protection components.

What is LX1LD020's listed category?

The category is 22384-STARTERS,INTEGRAL,ACCESS — it is an accessory coil for integral combination starters.

MPN
LX1LD020