The Telemecanique LX1LD030 is a replacement coil for the TeSys Integral series of contactors and motor starters. It is wound for 36 V AC at 60 Hz control voltage, drawing 420 to 500 VA inrush and 24 to 36 VA holding at 60 Hz with a power factor of 0.55 and 0.28 respectively.
TeSys LX1LD030 Coil, 36 V AC 60 Hz, Obsolete
MPNLX1LD030
Obsolete
Telemecanique TeSys Integral replacement coil, LX1LD030, 36 V AC 60 Hz, 0.503 Ohm, obsolete.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product type | Coil |
| Product range | TeSys |
| Device short name | LX1 |
| Parameter | Value |
|---|---|
| Control circuit voltage [Uc] | 36 V AC 60 Hz |
| Control circuit type | AC 60 Hz |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc (at Drop-out: 0.25...0.7 Uc (at <131 °F (55 °C)) |
| Coil resistance (avg.) | 0.503 Ohm 68 °F (20 °C) |
| Coil inductance (closed circuit) | 0.106 H |
| Parameter | Value |
|---|---|
| Inrush power (VA) | 420...500 VA 60 Hz cos phi 0.55 |
| Hold-in power (VA) | 24...36 VA 60 Hz cos phi 0.28 |
Product details
Frequently asked questions
What is the control voltage and frequency for LX1LD030?
36 V AC at 60 Hz. The coil operates between 0.85 and 1.1 times the rated voltage (30.6 to 39.6 V AC) and drops out between 0.25 and 0.7 times rated (9 to 25.2 V AC) at up to 131 °F.
What is the coil resistance and power draw?
Average resistance is 0.503 Ohm at 68 °F. Inrush power is 420 to 500 VA at 60 Hz; hold-in power is 24 to 36 VA at 60 Hz.
MPN
LX1LD030