The LX1LD040 is a replacement coil for the TeSys Integral series of contactors and motor starters. It is a 48 V AC 60 Hz control circuit coil. The coil draws 420-500 VA inrush at 60 Hz with a 0.55 power factor, then settles to 24-36 VA hold-in power at 0.28 power factor. Coil resistance is 0.845 Ohm at 68 °F (20 °C). This is a low-resistance winding for a 48 V AC coil, consistent with the high inrush current. The inductance of the closed circuit is 0.106 H, which governs the magnetic latching once the armature seats.
Control voltage limits and operating window
The coil operates between 0.85 and 1.1 times the rated control voltage (Uc) at up to 131 °F (55 °C). Drop-out occurs between 0.25 and 0.7 Uc.