Schneider Electric LX1LD0489 — Contactor & Starter Coils

Schneider Electric LX1LD0489 TeSys Integral Coil, 48 V AC 50

MPNLX1LD0489
Active

Schneider Electric TeSys Integral replacement coil, LX1LD0489, 48 V AC 50 Hz, 350-400 VA inrush, 20-30 VA hold-in.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1LD0489 — Identification
ParameterValue
Product typeCoil
Product rangeTeSys
Device short nameLX1
LX1LD0489 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at Drop-out: 0.25...0.7 Uc (at <131 °F (55 °C))
Coil resistance (avg.)1.26 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)0.29 H
LX1LD0489 — Power & Thermal
ParameterValue
Inrush power (VA)350...400 VA 50 Hz cos phi 0.55
Hold-in power (VA)20...30 VA 50 Hz cos phi 0.28

Product details

The LX1LD0489 is a replacement coil for the TeSys Integral line of combination starters — the ones that pack a contactor, overload relay, and disconnect into one DIN-rail footprint. It's the part you order when the original coil opens or the control voltage changes and you're keeping the existing starter base. Rated for 48 V AC 50 Hz control circuits. Inrush draws 350-400 VA at cos phi 0.55; once sealed, the hold-in drops to 20-30 VA at cos phi 0.28. That inrush-to-hold ratio is typical of AC-operated contactor coils — the control transformer sizing needs to cover the inrush peak, not just the sealed VA. Operational voltage window is 0.85 to 1.1 times Uc (40.8 to 52.8 V AC). Drop-out range is 0.25 to 0.7 times Uc (12 to 33.6 V AC) at up to 55 °C. If your line voltage sags below 40.8 V during a brownout, the coil may drop out and the starter opens — that's by design, not a fault.

If you're replacing an existing unit, verify the coil resistance (1.26 Ohm at 20 °C) and closed-circuit inductance (0.29 H) against your starter base to confirm the magnetic circuit matches.

Physical and electrical notes

Single unit per package. The coil is a drop-in replacement for the TeSys Integral starter — no modification to the base or wiring required. The 48 V AC winding is designed for 50 Hz supply; operating at 60 Hz will shift the impedance and may reduce pull-in force, so confirm the control transformer frequency matches. Resistance measured at 1.26 Ohm at 68 °F (20 °C). Use this as a bench-check value when troubleshooting a coil that won't pull in — a shorted turn will read significantly lower, an open winding will read infinite.

Frequently asked questions

What is the control voltage and frequency for this coil?

Rated 48 V AC at 50 Hz. Inrush is 350-400 VA, hold-in is 20-30 VA. Operational range is 0.85 to 1.1 times Uc (40.8 to 52.8 V AC).

What TeSys range does this coil belong to?

It is part of the TeSys Integral range — the combination starter family that integrates a contactor, overload relay, and disconnect into a single unit.

What is the coil resistance and inductance?

Average resistance is 1.26 Ohm at 68 °F (20 °C). Inductance of the closed circuit is 0.29 H.