Skip to main content
Schneider Electric LX1LD190 — Contactor & Starter Coils

Schneider LX1LD190 TeSys Integral Coil, 230-240 VAC 60 Hz

MPNLX1LD190
Obsolete

Schneider Electric TeSys LX1LD190 replacement coil, 230-240 V AC 60 Hz control circuit, 420-500 VA inrush, 24-36 VA hold-in, for Integral starters.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LX1LD190 — Identification
ParameterValue
Product typeCoil
Product rangeTeSys
Device short nameLX1
LX1LD190 — Electrical
ParameterValue
Control circuit voltage [Uc]230...240 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at Drop-out: 0.25...0.7 Uc (at <131 °F (55 °C))
Coil resistance (avg.)23.24 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)4.5 H
LX1LD190 — Power & Thermal
ParameterValue
Inrush power (VA)420...500 VA 60 Hz cos phi 0.55
Hold-in power (VA)24...36 VA 60 Hz cos phi 0.28

Product details

What This Coil Does in the Panel

The LX1LD190 is a replacement coil for Schneider Electric TeSys Integral starters, designed to pull in and hold the contactor armature on a 230-240 V AC 60 Hz control circuit. At inrush it draws 420-500 VA at 60 Hz with a 0.55 power factor — the surge is brief but the control transformer must be sized to deliver that without dropping below the 0.85 Uc dropout threshold. Once sealed, hold-in consumption drops to 24-36 VA at 0.28 power factor, with a closed-circuit inductance of 4.5 H and a DC resistance of 23.24 Ω at 20°C.

Sourcing Reality — Obsolete, No Direct Successor

Schneider lists the LX1LD190 as obsolete. For a BOM line that needs this exact coil, the only channel is independent surplus or broker stock. Availability is lot-specific and confirmed at RFQ; quantities are not held in regular distribution. If you are evaluating a board spin or panel redesign, the functional replacement is a different coil form factor — the LX1LD190's mounting and electrical interface are specific to the Integral platform, not the current TeSys island or TeSys GV series.

Frequently asked questions

How can I source the LX1LD190 for a repair or BOM fill?

Through independent surplus and broker channels. No stock is held in standard distribution.

MPN