Schneider Electric LX4D6DD — Contactor & Starter Coils

Schneider LX4D6DD TeSys contactor coil, 96 V DC

MPNLX4D6DD
Active

Schneider Electric TeSys LX4D6DD replacement contactor coil, 96 V DC control circuit, 51.9 Ohm resistance, 10 Mcycles mechanical durability.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX4D6DD — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D6
Coil technologyWithout built-in suppressor module
LX4D6DD — Electrical
ParameterValue
Control circuit voltage [Uc]96 V DC
Coil resistance (avg.)51.9 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)4.18 H
LX4D6DD — Performance & Durability
ParameterValue
Max. operating rate3600 cyc/h 140 °F (60 °C)
Mechanical durability10 Mcycles
LX4D6DD — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

The LX4D6DD is a replacement contactor coil from the Schneider TeSys range, designed to fit LX1D6 contactors. It operates on a 96 V DC control circuit, drawing current determined by its 51.9 Ohm resistance at 20 °C and 4.18 H inductance when the contactor is closed. Rated for 10 Mcycles mechanical durability and a maximum operating rate of 3600 cycles per hour at 60 °C, this coil suits high-cycling applications like conveyor sorting stations or packaging machinery where the contactor opens and closes repeatedly across a shift.

Coil suppression — what the listing tells you

This coil ships without a built-in suppressor module. That means the installer must add an external flyback diode or RC snubber across the coil terminals to suppress the inductive kickback when the DC circuit opens. Without it, the voltage spike can damage PLC output cards or relay contacts driving the coil. The 4.18 H inductance of the closed circuit gives a stored energy of roughly 0.5 J at 96 V — enough to arc across a relay contact if unsuppressed. A standard 1N4007 diode reverse-biased across the coil handles this, but verify polarity: cathode to positive rail.

Frequently asked questions

What is the closest pin-compatible alternative to LX4D6DD in this component family?

Within the TeSys D range, the LX4D6DD is the 96 V DC coil variant for LX1D6 contactors. Other voltage variants (e.g., 24 V DC, 48 V DC, 110 V DC) share the same mechanical footprint and mounting but differ in coil resistance and inductance. No direct pin-compatible alternative exists at the same voltage — the 96 V DC coil is specific to this control circuit voltage.

What is LX4D6DD's listed range (TeSys) on this component line?

The LX4D6DD belongs to the Schneider TeSys range, specifically the TeSys D series of contactors and replacement parts. The device short name is LX1D6, indicating it mates with the corresponding LX1D6 contactor base.

What compliance documentation does this brand provide for LX4D6DD?

Schneider Electric typically provides RoHS and REACH declarations for TeSys components. The LX4D6DD falls under the 18401-WORLD SERVICE PARTS category, which includes standard compliance documentation. Specific UL or IEC certification files are available through Schneider's documentation portal for the TeSys D series.

MPN
LX4D6DD